MEAN WELL DDR-480 series: DIN Rail DC/DC Converter - DDR-480B-24

Description

The MEAN WELL DDR-480B-24 is a fanless DIN rail DC/DC converter rated at 24 V, 20 A and 480 W. Its B-code input supports 16.8–33.6 VDC continuously, with a separate 14.4–16.8 VDC band for 100 ms. The metal enclosure provides reinforced 4 kVDC input-to-output isolation, adjustable output, a DC OK relay, remote ON/OFF and active current sharing. A 720 W peak is available for up to 5 seconds under the specified temperature and loading conditions.

Product Datasheet

Download MEAN WELL DDR-480 Datasheet (PDF)

The DDR-480 section is on PDF pages 32, 33, 34, 35, 36, 37, 38, 39, 40. Refer to the complete mechanical drawings and notes when planning installation.

Model and Output Ratings

Full model DDR-480B-24
Series DDR-480
Input code B
DC output voltage 24 V
Rated output current 20 A
Rated output power 480 W
Output current range 0–20 A
Output voltage adjustment range 24–28 V
Peak output current 30 A
Peak output power 720 W
Peak duration 5 seconds maximum
Maximum ripple and noise 120 mVp-p
Voltage tolerance ±1.0%
Line regulation ±0.5%
Load regulation ±1.0%

Adjust the output with the front-panel Vo Adj. control and retain the current, power and thermal limits. The adjustment range is the specified voltage interval.

Suitable applications include railway and industrial control, security, factory automation and telecommunications. The converter can provide DC voltage conversion, additional input/output insulation and compensation for cable voltage drop within its adjustment range.

Input and Hold-up Performance

Continuous DC input range 16.8–33.6 VDC
100 ms input range 14.4–16.8 VDC
Reference DC input 24 VDC
Typical efficiency 91%
Typical DC input current 23 A at 24 VDC
Typical inrush current 30 A
Set-up / rise time 500 / 60 ms
Minimum hold-up at 100% load 10 ms at 24 VDC
Minimum hold-up at 70% load 16 ms at 24 VDC
Supply interruption classification EN 50155:2021, S2; 10 ms at full load
Normal measurement conditions 24 VDC input, rated load and 25°C ambient

The 100 ms low-input band is a short-duration condition and does not extend the continuous input range. Apply the separate input-voltage derating curve before selecting the load.

Use the dedicated model hold-up-versus-load curve for other load levels. A larger hold-up duration at reduced load is not a full-load rating.

Ripple and noise are measured at 20 MHz bandwidth using a 12-inch twisted pair terminated by parallel 0.1 µF and 47 µF capacitors. Voltage tolerance includes set-up tolerance, line regulation and load regulation.

Peak Loading and Protection

Peak loading capability 150% of the model rated output power for the stated peak duration
Protection functions Short circuit, overload, overvoltage, overtemperature, input reverse polarity and input undervoltage
Sustained overload response Constant-current limiting at 105–135% of rated output power; automatic recovery after the overload is removed
Overvoltage threshold 28.8–35 V
Overvoltage recovery Output shutdown; reapply input power to recover
Overtemperature recovery Output shutdown; reapply input power to recover
Input undervoltage turn-on specification ≥16.8 VDC
Input undervoltage turn-off specification ≤16.5 VDC
Input undervoltage recovery Automatic when the input rises above the operating threshold
Internal input fuse reference 5 × Conquer MST, 10 A, 250 V; time-lag

The catalogue loading example shows 480 W for 100 seconds followed by 720 W for 5 seconds. These are conditional pulse-load patterns; peak power is not a continuous rating. Apply the peak-temperature curve as well as the continuous-load limits.

After the initial peak interval, a sustained overload enters the specified constant-current protection region. Keep planned peaks within 5 seconds; the overload-protection response does not authorize a longer peak interval.

Two MOSFETs in series with the negative input prevent output when input polarity is reversed. Correct the polarity before restoring operation.

A start-up resistor limits inrush current and is then bypassed by MOSFETs. The fuse references identify internal protection components; they are not an external fuse-selection instruction.

Current Sharing

Maximum parallel units 4
Output-voltage matching Difference strictly less than 0.2 V
Total output-current limit Rated current per unit × number of units × 0.9
Minimum parallel load Strictly greater than 3% × rated current per unit × number of units
Four-unit current limit at the stated unit ratings 72 A
Current-sharing connections Connect P+ to P+ and P− to P− across all participating units

The series specification describes current sharing up to 1920 W (3+1 units). Size the usable load with the 0.9 current formula, the actual model rating and all applicable derating conditions. The headline aggregate rating is not an unconditional usable load or N+1 capacity guarantee.

Use matching output-voltage units, connect the outputs and sharing terminals as illustrated, and adjust their output-voltage differences to less than 0.2 V. Consult the manufacturer for arrangements beyond four units.

DC OK Relay and Remote ON/OFF

DC OK contact closed Power supply on / DC OK
DC OK contact open Power supply off / DC fail
Maximum DC OK contact rating 30 VDC, 1 A resistive load
Remote-control terminals TB1 pin 4 relative to TB1 pin 2 (−Vin)
Output ON Remote input open, or 5.5–10 VDC
Output OFF Remote input shorted, or 0–0.8 VDC
Front-panel indication DC OK indicator

Observe the relay contact rating when connecting an external monitoring circuit. Remote ON/OFF controls the converter output; disconnect the DC input before installing or servicing wiring.

Terminal Assignment and Wiring

TB1 pin 1 FG / protective earth
TB1 pin 2 DC input −Vin
TB1 pin 3 DC input +Vin
TB1 pin 4 Remote ON/OFF
TB2 pins 1, 2 DC output +Vo
TB2 pins 3, 4 DC output −Vo
TB2 pins 5, 6 DC OK relay contact
TB2 pin 7 P+ current sharing
TB2 pin 8 P− current sharing

Observe the numbered terminals in the mechanical drawing. Connect FG to the installation protective-earth system and size the DC conductors and terminations for this model’s input and output currents.

Keep the DC OK contacts separate from the DC power and current-sharing connections. Allow access to the terminals, Vo Adj. control and rail latch after installation.

Cooling, Temperature and Input Derating

Cooling Free-air convection; fanless
Required orientation for the published curves Vertical
Working ambient range −40 to +80°C, subject to derating
Continuous-load temperature curve 100% through 55°C; reduce along the plotted line to 40% at 80°C
Full 150% peak temperature range −40 to +60°C, within the peak-duration limit
Load at minimum continuous input 80%
Input for 100% load 21.6 VDC and above within the continuous input range
Operating altitude Up to 5000 m; overvoltage category II
Altitude temperature derating Above 2000 m: reduce permitted ambient temperature by 3.5°C per additional 1000 m

Input-voltage and temperature limits apply together. At low input, follow the rising input-derating line between the minimum continuous voltage and the full-load input point; short-duration input operation is not a full-load continuous extension.

Above 60°C, reduce the allowed 5-second peak along its separate upper curve to 40% load at 80°C. The model-specific continuous-load curve remains a separate constraint.

Provide unobstructed airflow around the installed converter. Do not treat the ambient range, peak capability or altitude statement as an unconditional full-load rating.

Environmental and Mechanical Data

Working humidity 5–95% RH, non-condensing
Storage temperature / humidity −40 to +85°C; 5–95% RH, non-condensing
Temperature coefficient ±0.03%/°C over 0–55°C
Component vibration 10–500 Hz, 5 G; 10 minutes per cycle; 60 minutes on each X, Y and Z axis
Vibration mounting requirement Compliance with IEC 61373
Catalogue body dimensions, W × H × D 85.5 × 125.2 × 129.2 mm
Case reference 984F
Drawing tolerance ±1 mm
DIN rail compatibility TS35/7.5 or TS35/15
Rail supply status Reference rail shown; not included with the unit
Unit mass, catalogue PACKING reference 1375 g
Catalogue packing 1.375 kg; 8 units / 12 kg / 0.95 CUFT
Minimum MTBF 750.3K hours, Telcordia SR-332 (Bellcore); 101.7K hours, MIL-HDBK-217F at 25°C
Nominal switching frequency 65 kHz
Catalogue warranty 3 years

Use the illustrated DIN rail mounting and removal arrangement. The body dimensions do not include the installed rail, external wiring or cable-bend clearance. Select the rail and installation hardware for the enclosure.

The listed mass is the explicit per-unit catalogue packing reference; it is not a measured installation mass or the gross mass of an individual shipping box.

Safety, Isolation and EMC

Catalogue-listed safety approvals IEC 62368-1; UL 62368-1; AS/NZS 62368-1; EAC TP TC 004
Input-to-output isolation 4 kVDC; reinforced isolation
Input-to-FG withstand voltage 2.5 kVDC
Output-to-FG withstand voltage 0.71 kVDC
Isolation resistance >100 MΩ between input–output, input–FG and output–FG at 500 VDC, 25°C and 70% RH
Conducted emissions BS EN / EN 55032, Class A
Radiated emissions BS EN / EN 55032, Class B
Immunity standards BS EN / EN 55035
Railway standards BS EN / EN 50155; IEC 60571; IEC 61373 shock and vibration; BS EN / EN 50121-3-2 EMC; BS EN / EN 45545-2 fire protection

The six listed immunity tests use criterion A: ESD level 3 at 8 kV air and 6 kV contact; radiated RF level 3 at 10 V/m; EFT/burst level 3 at 2 kV; surge level 3 at 1 kV line–line and 2 kV line–line–FG; conducted RF level 3 at 10 V; and magnetic field level 4 at 30 A/m.

The emissions table names BS EN / EN 61000-3-3 for voltage flicker without a numerical test level; it does not specify a harmonic-current limit. Confirm EMC compliance of the complete equipment after integration.

Railway Environmental and Fire Tests

The catalogue reports PASS for EN 50155 dry heat (section 13.4.5: 70°C for 6 hours and 85°C for 10 minutes); cyclic damp heat (13.4.8: 25–55°C, 90–100% RH, 48 hours); vibration (13.4.10: 19°C, 65% RH, 10 minutes); shock (13.4.10: 21 ±3°C, 65 ±5% RH, 30 ms ×18); low-temperature storage (13.4.6: −40°C, 16 hours); and salt mist (13.4.13: 35 ±2°C, 96 hours). These test conditions do not expand continuous operating limits.

EN 45545-2:2020 results are marked PASS at HL1, HL2 and HL3 for all listed items: PCB R22 oxygen index, smoke density and smoke toxicity; PCB R24 oxygen index; PCB R25 glow-wire; potting R24 oxygen index; and terminal-block R26 vertical flame. Test methods are EN ISO 4589-2:2017, EN ISO 5659-2:2017, EN 17084:2018, EN 60695-2-11:2014 and EN 60695-11-10:2013 as applicable. Component results do not certify the entire vehicle or equipment.

MEAN WELL DDR-480 series: DIN Rail DC/DC Converter - DDR-480B-24

Product form

The MEAN WELL DDR-480B-24 is a fanless DIN rail DC/DC converter rated at 24 V, 20 A and 480 W.... Read more

$488.42 Incl. VAT

    • Guaranteed secure & safe checkout.

      shop pay

    Description

    The MEAN WELL DDR-480B-24 is a fanless DIN rail DC/DC converter rated at 24 V, 20 A and 480 W. Its B-code input supports 16.8–33.6 VDC continuously, with a separate 14.4–16.8 VDC band for 100 ms. The metal enclosure provides reinforced 4 kVDC input-to-output isolation, adjustable output, a DC OK relay, remote ON/OFF and active current sharing. A 720 W peak is available for up to 5 seconds under the specified temperature and loading conditions.

    Product Datasheet

    Download MEAN WELL DDR-480 Datasheet (PDF)

    The DDR-480 section is on PDF pages 32, 33, 34, 35, 36, 37, 38, 39, 40. Refer to the complete mechanical drawings and notes when planning installation.

    Model and Output Ratings

    Full model DDR-480B-24
    Series DDR-480
    Input code B
    DC output voltage 24 V
    Rated output current 20 A
    Rated output power 480 W
    Output current range 0–20 A
    Output voltage adjustment range 24–28 V
    Peak output current 30 A
    Peak output power 720 W
    Peak duration 5 seconds maximum
    Maximum ripple and noise 120 mVp-p
    Voltage tolerance ±1.0%
    Line regulation ±0.5%
    Load regulation ±1.0%

    Adjust the output with the front-panel Vo Adj. control and retain the current, power and thermal limits. The adjustment range is the specified voltage interval.

    Suitable applications include railway and industrial control, security, factory automation and telecommunications. The converter can provide DC voltage conversion, additional input/output insulation and compensation for cable voltage drop within its adjustment range.

    Input and Hold-up Performance

    Continuous DC input range 16.8–33.6 VDC
    100 ms input range 14.4–16.8 VDC
    Reference DC input 24 VDC
    Typical efficiency 91%
    Typical DC input current 23 A at 24 VDC
    Typical inrush current 30 A
    Set-up / rise time 500 / 60 ms
    Minimum hold-up at 100% load 10 ms at 24 VDC
    Minimum hold-up at 70% load 16 ms at 24 VDC
    Supply interruption classification EN 50155:2021, S2; 10 ms at full load
    Normal measurement conditions 24 VDC input, rated load and 25°C ambient

    The 100 ms low-input band is a short-duration condition and does not extend the continuous input range. Apply the separate input-voltage derating curve before selecting the load.

    Use the dedicated model hold-up-versus-load curve for other load levels. A larger hold-up duration at reduced load is not a full-load rating.

    Ripple and noise are measured at 20 MHz bandwidth using a 12-inch twisted pair terminated by parallel 0.1 µF and 47 µF capacitors. Voltage tolerance includes set-up tolerance, line regulation and load regulation.

    Peak Loading and Protection

    Peak loading capability 150% of the model rated output power for the stated peak duration
    Protection functions Short circuit, overload, overvoltage, overtemperature, input reverse polarity and input undervoltage
    Sustained overload response Constant-current limiting at 105–135% of rated output power; automatic recovery after the overload is removed
    Overvoltage threshold 28.8–35 V
    Overvoltage recovery Output shutdown; reapply input power to recover
    Overtemperature recovery Output shutdown; reapply input power to recover
    Input undervoltage turn-on specification ≥16.8 VDC
    Input undervoltage turn-off specification ≤16.5 VDC
    Input undervoltage recovery Automatic when the input rises above the operating threshold
    Internal input fuse reference 5 × Conquer MST, 10 A, 250 V; time-lag

    The catalogue loading example shows 480 W for 100 seconds followed by 720 W for 5 seconds. These are conditional pulse-load patterns; peak power is not a continuous rating. Apply the peak-temperature curve as well as the continuous-load limits.

    After the initial peak interval, a sustained overload enters the specified constant-current protection region. Keep planned peaks within 5 seconds; the overload-protection response does not authorize a longer peak interval.

    Two MOSFETs in series with the negative input prevent output when input polarity is reversed. Correct the polarity before restoring operation.

    A start-up resistor limits inrush current and is then bypassed by MOSFETs. The fuse references identify internal protection components; they are not an external fuse-selection instruction.

    Current Sharing

    Maximum parallel units 4
    Output-voltage matching Difference strictly less than 0.2 V
    Total output-current limit Rated current per unit × number of units × 0.9
    Minimum parallel load Strictly greater than 3% × rated current per unit × number of units
    Four-unit current limit at the stated unit ratings 72 A
    Current-sharing connections Connect P+ to P+ and P− to P− across all participating units

    The series specification describes current sharing up to 1920 W (3+1 units). Size the usable load with the 0.9 current formula, the actual model rating and all applicable derating conditions. The headline aggregate rating is not an unconditional usable load or N+1 capacity guarantee.

    Use matching output-voltage units, connect the outputs and sharing terminals as illustrated, and adjust their output-voltage differences to less than 0.2 V. Consult the manufacturer for arrangements beyond four units.

    DC OK Relay and Remote ON/OFF

    DC OK contact closed Power supply on / DC OK
    DC OK contact open Power supply off / DC fail
    Maximum DC OK contact rating 30 VDC, 1 A resistive load
    Remote-control terminals TB1 pin 4 relative to TB1 pin 2 (−Vin)
    Output ON Remote input open, or 5.5–10 VDC
    Output OFF Remote input shorted, or 0–0.8 VDC
    Front-panel indication DC OK indicator

    Observe the relay contact rating when connecting an external monitoring circuit. Remote ON/OFF controls the converter output; disconnect the DC input before installing or servicing wiring.

    Terminal Assignment and Wiring

    TB1 pin 1 FG / protective earth
    TB1 pin 2 DC input −Vin
    TB1 pin 3 DC input +Vin
    TB1 pin 4 Remote ON/OFF
    TB2 pins 1, 2 DC output +Vo
    TB2 pins 3, 4 DC output −Vo
    TB2 pins 5, 6 DC OK relay contact
    TB2 pin 7 P+ current sharing
    TB2 pin 8 P− current sharing

    Observe the numbered terminals in the mechanical drawing. Connect FG to the installation protective-earth system and size the DC conductors and terminations for this model’s input and output currents.

    Keep the DC OK contacts separate from the DC power and current-sharing connections. Allow access to the terminals, Vo Adj. control and rail latch after installation.

    Cooling, Temperature and Input Derating

    Cooling Free-air convection; fanless
    Required orientation for the published curves Vertical
    Working ambient range −40 to +80°C, subject to derating
    Continuous-load temperature curve 100% through 55°C; reduce along the plotted line to 40% at 80°C
    Full 150% peak temperature range −40 to +60°C, within the peak-duration limit
    Load at minimum continuous input 80%
    Input for 100% load 21.6 VDC and above within the continuous input range
    Operating altitude Up to 5000 m; overvoltage category II
    Altitude temperature derating Above 2000 m: reduce permitted ambient temperature by 3.5°C per additional 1000 m

    Input-voltage and temperature limits apply together. At low input, follow the rising input-derating line between the minimum continuous voltage and the full-load input point; short-duration input operation is not a full-load continuous extension.

    Above 60°C, reduce the allowed 5-second peak along its separate upper curve to 40% load at 80°C. The model-specific continuous-load curve remains a separate constraint.

    Provide unobstructed airflow around the installed converter. Do not treat the ambient range, peak capability or altitude statement as an unconditional full-load rating.

    Environmental and Mechanical Data

    Working humidity 5–95% RH, non-condensing
    Storage temperature / humidity −40 to +85°C; 5–95% RH, non-condensing
    Temperature coefficient ±0.03%/°C over 0–55°C
    Component vibration 10–500 Hz, 5 G; 10 minutes per cycle; 60 minutes on each X, Y and Z axis
    Vibration mounting requirement Compliance with IEC 61373
    Catalogue body dimensions, W × H × D 85.5 × 125.2 × 129.2 mm
    Case reference 984F
    Drawing tolerance ±1 mm
    DIN rail compatibility TS35/7.5 or TS35/15
    Rail supply status Reference rail shown; not included with the unit
    Unit mass, catalogue PACKING reference 1375 g
    Catalogue packing 1.375 kg; 8 units / 12 kg / 0.95 CUFT
    Minimum MTBF 750.3K hours, Telcordia SR-332 (Bellcore); 101.7K hours, MIL-HDBK-217F at 25°C
    Nominal switching frequency 65 kHz
    Catalogue warranty 3 years

    Use the illustrated DIN rail mounting and removal arrangement. The body dimensions do not include the installed rail, external wiring or cable-bend clearance. Select the rail and installation hardware for the enclosure.

    The listed mass is the explicit per-unit catalogue packing reference; it is not a measured installation mass or the gross mass of an individual shipping box.

    Safety, Isolation and EMC

    Catalogue-listed safety approvals IEC 62368-1; UL 62368-1; AS/NZS 62368-1; EAC TP TC 004
    Input-to-output isolation 4 kVDC; reinforced isolation
    Input-to-FG withstand voltage 2.5 kVDC
    Output-to-FG withstand voltage 0.71 kVDC
    Isolation resistance >100 MΩ between input–output, input–FG and output–FG at 500 VDC, 25°C and 70% RH
    Conducted emissions BS EN / EN 55032, Class A
    Radiated emissions BS EN / EN 55032, Class B
    Immunity standards BS EN / EN 55035
    Railway standards BS EN / EN 50155; IEC 60571; IEC 61373 shock and vibration; BS EN / EN 50121-3-2 EMC; BS EN / EN 45545-2 fire protection

    The six listed immunity tests use criterion A: ESD level 3 at 8 kV air and 6 kV contact; radiated RF level 3 at 10 V/m; EFT/burst level 3 at 2 kV; surge level 3 at 1 kV line–line and 2 kV line–line–FG; conducted RF level 3 at 10 V; and magnetic field level 4 at 30 A/m.

    The emissions table names BS EN / EN 61000-3-3 for voltage flicker without a numerical test level; it does not specify a harmonic-current limit. Confirm EMC compliance of the complete equipment after integration.

    Railway Environmental and Fire Tests

    The catalogue reports PASS for EN 50155 dry heat (section 13.4.5: 70°C for 6 hours and 85°C for 10 minutes); cyclic damp heat (13.4.8: 25–55°C, 90–100% RH, 48 hours); vibration (13.4.10: 19°C, 65% RH, 10 minutes); shock (13.4.10: 21 ±3°C, 65 ±5% RH, 30 ms ×18); low-temperature storage (13.4.6: −40°C, 16 hours); and salt mist (13.4.13: 35 ±2°C, 96 hours). These test conditions do not expand continuous operating limits.

    EN 45545-2:2020 results are marked PASS at HL1, HL2 and HL3 for all listed items: PCB R22 oxygen index, smoke density and smoke toxicity; PCB R24 oxygen index; PCB R25 glow-wire; potting R24 oxygen index; and terminal-block R26 vertical flame. Test methods are EN ISO 4589-2:2017, EN ISO 5659-2:2017, EN 17084:2018, EN 60695-2-11:2014 and EN 60695-11-10:2013 as applicable. Component results do not certify the entire vehicle or equipment.