| Installation isolation |
Disconnect the utility supply and prevent inadvertent reconnection before installation or maintenance. Have faults examined by a qualified technician; do not open the power-supply case yourself. |
| Mounting screws |
Maintain adequate insulation between mounting screws and internal components. Confirm the permitted screw length and supplied mounting hardware with MEAN WELL before installation. |
| Ventilation and nearby heat sources |
Keep ventilation openings unobstructed. Maintain 10–15 cm clearance when the adjacent device is a heat source, in addition to this model’s specified installation clearances. |
| Conductor and terminal installation |
Select conductors for the actual current and temperature conditions. The installation manual requires each wire to carry no more than 80% of its suggested wire-table current when five or more wires are connected to the unit. Keep every strand inside its terminal and secure all terminal connections. |
| Protective earth and system verification |
Connect AC/L to live, AC/N to neutral and FG to protective earth according to the model’s terminal diagram. Verify EMC again in the completed equipment. |
| Environment and load limits |
Do not install the unit in high-moisture locations or near water, fire, or temperatures above its specified ambient limit. Keep output current and power within this model’s rated and derated limits. |
| Specified installation position |
Install upright; forward tilt, backward tilt and flat mounting are not permitted. Keep at least 10 cm clearance above, below, left and right, and 5 cm at the ventilation-hole side. Outdoor installation requires a sheltered location. |
| Terminal screw guidance |
The enclosed-type installation manual lists #6 terminal screws and a suggested torque of 8–10 for ERP-350, but that table does not print a torque unit. Confirm the unit and supplied terminal hardware with MEAN WELL before tightening. |