MEAN WELL HDR-100-48N is a 48 VDC, 2.1 A, 100.8 W single-output DIN rail AC/DC power supply. Its 70 mm-wide plastic Class II housing mounts on TS-35/7.5 or TS-35/15 rails and cools by free-air convection. This N-suffix version is non-LPS, with a 43.2–55.2 V adjustment range, power-ON LED and model-specific protection limits.
Product Datasheet
Download MEAN WELL HDR-100 Datasheet (PDF)
The HDR-100 section is on PDF pages 13, 14, 15, 16. Refer to the complete mechanical drawings and notes when planning installation.
Exact Model and Output
| Complete model / suffix |
The complete HDR-100-48N code selects the 48 V output and the N-suffix configuration. Non-LPS; its permitted voltage adjustment is 43.2–55.2 V. |
| Rated DC output |
48 V; 2.1 A; 100.8 W. Output current range: 0–2.1 A. Use these exact model ratings with the derating limits below. |
| Voltage adjustment |
43.2–55.2 V. Observe the rated current and power limits when adjusting output voltage. |
| Ripple and noise |
240 mVp-p maximum; 20 MHz bandwidth, a 12-inch twisted pair and parallel 0.1 µF / 47 µF capacitors. |
| Accuracy / regulation |
Voltage tolerance ±1.0%; line regulation ±1.0%; load regulation ±1.0%. Tolerance includes setup, line and load regulation. |
| Typical efficiency |
90% at the default test conditions. |
Unless otherwise stated, specifications are measured at 230 VAC input, rated load and 25°C ambient. HDR-100 is the family designation; use the exact voltage, current and wattage for this model.
Input, Timing and Low-load Operation
| Rated input range |
85–264 VAC or 120–370 VDC; 47–63 Hz AC. The catalogue additionally states operation at 277 VAC and 390 VDC. |
| Typical AC current |
3 A at 115 VAC; 1.6 A at 230 VAC. |
| Cold-start inrush |
35 A at 115 VAC; 70 A at 230 VAC, typical. |
| Setup / rise time |
500 ms / 60 ms at 230 VAC and 500 ms / 60 ms at 115 VAC, at full load. |
| Typical hold-up time |
30 ms at 230 VAC; 12 ms at 115 VAC, at full load. |
| No-load power |
Less than 0.3 W. |
The N suffix changes output performance and LPS status; it does not select a different AC/DC input-voltage range. Follow the actual unit marking and the applicable installation requirements for the approved installation.
Protection and Output Classification
| LPS configuration |
Non-LPS. Do not apply the blank-suffix LPS statement to this N model. |
| Short circuit / overload |
Short-circuit and overload protection; overload threshold 105–150% of rated output power. |
| Overload response |
Below 50% of rated output voltage: hiccup operation, with automatic recovery after the fault is removed. Within 50–100% of rated output voltage: constant-current limiting, with automatic recovery after the fault is removed. |
| Overvoltage |
56.5–64.8 V threshold; output shutdown, with re-powering required to recover. |
| Insulation class |
Class II insulation with a plastic housing. This insulation classification is separate from the limited-power-source classification. |
Protection thresholds describe fault response, not permitted continuous overload or an additional peak-power rating.
Cooling and Load Derating
| Cooling / orientation |
Free-air convection; the published curves are for vertical installation. Keep ventilation paths clear. |
| Ambient operating range |
−30°C to +70°C, subject to the input-specific thermal curve. |
| At 230 VAC input |
100% load through +50°C, then decreasing linearly to 50% at +70°C. |
| At 110 VAC input |
100% load through +45°C, then decreasing linearly to 50% at +70°C. |
| Input-voltage derating |
At 60 Hz, the curve rises from 80% load at 85 VAC to 100% at 115 VAC, and stays at 100% through the 277 VAC operational point. |
| Altitude / overvoltage category |
Operating altitude: 2000 m. Overvoltage category III according to EN61558, EN50178, EN60664-1 and EN62477-1, up to 2000 m. |
Apply input and ambient limits together. The catalogue’s general altitude note gives a 3.5°C ambient reduction per additional 1000 m for fanless models above 2000 m; this note does not by itself extend the stated 2000 m operating-altitude or category rating.
Confirm the permitted load for the actual enclosure, input voltage and unit marking. The maximum temperature is not a full-load guarantee.
DIN Rail, Terminals and Installation
| Compatible rail profiles |
TS-35/7.5 or TS-35/15, both 35 mm DIN rails. These are mounting profiles, not a supplied rail quantity or a separate MEAN WELL accessory order code. |
| Body / mounting space |
70 × 90 × 54.5 mm (W × H × D); 70 mm width equals 4SU. The dimension drawing has a general tolerance of ±0.5 mm and a 58.4 mm overall side-profile extent including the rear rail-mounting feature. |
| AC terminals |
Terminal 1: AC/L. Terminal 2: AC/N. |
| DC terminals |
Terminals 3 and 4: −V. Terminals 5 and 6: +V. |
| Local indication / adjustment |
Power-ON LED indicator and adjustable DC output voltage. |
| Accessories / external controls |
These pages identify the compatible rail profiles but no dedicated bracket, rail-adapter, cable or connector-kit order code. No remote-control, remote-sense, auxiliary-output or current-sharing interface is specified. |
Use the complete mounting and terminal drawing on PDF page 16. Follow the actual unit label and manufacturer installation manual for conductor type, terminal torque and approved installation conditions; illustrated label values must not be assumed to apply to every output variant.
The catalogue does not specify included rails or installation-hardware quantities. Installation and wiring clearance must keep ventilation and terminal access unobstructed.
Environment and Mechanical Reliability
| Humidity |
Operating: 20–90% RH, non-condensing. Storage: 10–95% RH, non-condensing. |
| Storage temperature |
−40°C to +85°C. |
| Temperature coefficient |
±0.03%/°C over 0–50°C. |
| Vibration |
10–500 Hz, 2G; 10 minutes per cycle, 60 minutes along each X, Y and Z axis. Mounting compliance: IEC60068-2-6. |
| Catalogue unit weight |
270 g (0.27 kg), catalogue packing reference per unit from the PACKING row; not a measured net or shipping weight. |
| Bulk packing reference |
48 pieces / 13.74 kg / 0.96 CUFT. The carton mass is not the individual unit weight or the quantity supplied with one product. |
| MTBF reference |
3271.9 K hours minimum, Telcordia SR-332 (Bellcore); 856.5 K hours minimum, MIL-HDBK-217F at 25°C. These are calculated reliability references, not guaranteed service life. |
Safety and EMC Conditions
| Safety standards listed |
UL62368-1, UL508, TUV BS EN/EN61558-2-16, BS EN/EN61558-1, IEC62368-1, EAC TP TC004, BSMI CNS15598-1, and BIS IS13252(Part1):2010 / IEC60950-1:2005 are listed as approved. Design reference: TUV BS EN/EN62368-1. |
| BIS marking condition |
The catalogue notes that some models may not carry the BIS logo. Confirm the required marking for the exact model and supplied unit. |
| Withstand / insulation |
Input-to-output: 4 kVAC; 100 MΩ insulation resistance at 500 VDC, 25°C and 70% RH. |
| Conducted / radiated emissions |
BS EN/EN55032 (CISPR32) and CNS15936, Class B. |
| Harmonic current / flicker |
BS EN/EN61000-3-2, Class A; BS EN/EN61000-3-3 for voltage flicker. For this N configuration, the harmonic-current test is at 90% load, as specified in note 4. |
| Immunity standards |
BS EN/EN55035, BS EN/EN61000-6-2 and BS EN/EN61204-3. |
| ESD |
BS EN/EN61000-4-2: level 3, 8 kV air; level 2, 4 kV contact; criteria A. |
| Radiated / burst immunity |
BS EN/EN61000-4-3 and -4: level 3, criteria A. |
| Surge immunity |
BS EN/EN61000-4-5: level 4, 2 kV line-to-neutral, criteria A. |
| Conducted / magnetic immunity |
BS EN/EN61000-4-6: level 3, criteria A. BS EN/EN61000-4-8: level 4, criteria A. |
| Voltage dips / interruptions |
BS EN/EN61000-4-11: >95% dip for 0.5 periods; 30% dip for 25 periods; >95% interruption for 250 periods. |
The supply is treated as an independent unit in the catalogue; the completed equipment must still be reconfirmed for compliance with the applicable EMC directives. Component-level listings do not certify the finished installation.
Application and Manufacturer Information
| Typical applications |
Household control systems, building automation, industrial control, factory automation and electro-mechanical apparatus. |
| Warranty statement |
The manufacturer catalogue lists a three-year warranty, subject to applicable manufacturer terms. |
| Catalogue reference |
HDR-100, revision 2026-04-03, PDF pages 13–16. |