MEAN WELL KAA-4R4V-S series: 4-channel KNX actuator and dimmer - KAA-4R4V-10S

Description

KAA-4R4V-10S — 4-channel KNX actuator and dimmer

MEAN WELL KAA-4R4V-10S combines four independent latching relays with four passive 0(1)–10 V current-sinking dimming channels. It is powered from the KNX bus and supports KNX Data Secure, linear or logarithmic dimming, panel operation, timers and scenes.

Download MEAN WELL KAA-4R4V-S Datasheet (PDF)
Download MEAN WELL KAA-4R4V-S Instruction Manual (PDF)

KAA-4R4V-S family: combined catalog pages 29–38, dated 2024-10-16. Use the correct current-rating column for this exact ordering code.

Model and control functions

Parameter Details
Model identity Manufacturer ordering code: KAA-4R4V-10S.
Supply method Powered by the EIB/KNX bus; no additional power supply is required.
Relay arrangement Four independent latching relays with four dimming-control channels. Select the required switching, dimming or shutter application in ETS.
Rated channel selection 10 A per channel. Observe the load-category, total-current and inrush limits below.
Configuration and manual operation Configure the application with ETS. Panel buttons provide manual operation and status indication. Time and scene functions are programmable.
KNX Data Secure The device certificate attached to the unit is required for the first secure configuration. After commissioning, remove it from the device as recommended and store it securely. Use a compatible application database and specialist KNX commissioning knowledge.
Dimming interface Four DC 0(1)–10 V passive current-sinking outputs for compatible LED drivers or electronic ballasts. This is a control interface, not an LED load power supply.
Dimming response Linear or logarithmic dimming curves are selectable in ETS. Each channel has a green status LED.
Communication functions Central manual enable, switching, absolute dimming and operation status; channel switching/status, relative and absolute dimming, scenes, automatic functions, blocking and staircase-light functions. The communication-object table also provides prewarning and permanent ON; use the application database for the applicable objects and flags.

Electrical and switching ratings

Parameter Details
KNX bus supply 21–31 VDC.
Bus current and power Below 14 mA; below 250 mW.
Relay output rating 230 VAC, 50 Hz; 10 A ohmic load per relay. Each relay is independent and potential-free.
Capacitive load 220 µF; the catalog identifies a Notified Body test report.
Maximum inrush current 400 A for a maximum 200 µs, or 80 A for a maximum 20 ms.
Load categories EN 60947-4-1: AC1 (cos φ = 0.8) 10 A; AC5a (cos φ = 0.45) 8 A; AC5b 10 A.
Maximum total current 40 A for the actuator; the per-channel rating does not override this aggregate limit.
Service life Mechanical: more than 10⁶ cycles. Electrical endurance EN 60669-1 section 19.1: 4 × 10⁴ cycles; fluorescent lamp (AX), section 19.2: 10⁴ cycles. The specified electrical tests have a Notified Body test report.
Shutter outputs Two paired shutter outputs.
Dimming output limit Four passive 0–10 V control outputs, maximum 50 mA sinking current per output.
Dimming cable length Up to 100 m at full control load with 1.5 mm² cable.
Control-device quantity Up to 500 drivers per dimming-control channel only when each driver sources 0.1 mA. Actual allowable quantity also depends on the installation, including total cable length. This is separate from relay switching capacity.

Load and driver selection

Parameter Details
Maximum load per channel Resistive load: 2300 W; incandescent lamps: 2300 W; 230 V halogen lamps: 2300 W; halogen electronic transformers: 1300 W; fluorescent lamps without compensation: 2000 W; parallel-compensated fluorescent lamps: 1200 W; maximum 15 electronic transformers; shutter motor: 600 W.
LED-driver quantity The following catalog values are maximum numbers of MEAN WELL LED power supplies per relay channel at 230 V. Respect the exact driver series, load, inrush and total-current limits; these are not counts for mixed-driver combinations.
Driver-count table, part 1 APC-8: 22; APC-12: 11; APC-16: 18; APC-25: 11; APC-35: 11; APC-8E: 22; APC-12E: 18; APC-16E: 15; APV-8: 22; APV-12: 11; APV-16: 18; APV-25: 11; APV-35: 11; APV-8E: 22; APV-12E: 18.
Driver-count table, part 2 APV-16E: 15; LCM-25: 25; LCM-40: 25; LCM-60: 25; LCM-25DA: 25; LCM-40DA: 25; LCM-60DA: 25; LPC-20: 11; LPC-35: 9; LPC-60: 8; LPC-100: 7; LPC-150: 5; LPF-16: 18; LPF-25: 16; LPF-40: 16.
Driver-count table, part 3 LPF-60: 9; LPF-90: 7; LPF-16D: 18; LPF-25D: 16; LPF-40D: 16; LPF-60D: 9; LPF-90D: 7; LPH-18: 16; LPHC-18: 16; LPV-20: 11; LPV-35: 9; LPV-60: 8; LPV-100: 7; LPV-150: 8; NPF-40: 10.
Driver-count table, part 4 NPF-60: 10; NPF-90: 8; NPF-120: 8; NPF-40D: 10; NPF-60D: 10; NPF-90D: 8; NPF-120D: 8; PCD-16B: 80; PCD-25B: 53; PCD-40B: 45; PCD-60B: 26; PLC-30: 23; PLC-45: 23; PLC-60: 23; PLC-100: 13.
Driver-count table, part 5 PLD-16B: 40; PLD-25: 32; PLD-40B: 32; PLD-60B: 32; PLM-12: 53; PLM-25: 53; PLM-40: 53; PLN-20: 23; PLN-30: 23; PLN-45: 23; PLN-60: 23; PLN-100: 13; PLP-30: 32; PLP-45: 27; PLP-60: 23.
Driver-count table, part 6 PWM-40: 10; PWM-60: 10; PWM-90: 8; PWM-120: 8; HLN-40H: 10; HLN-60H: 9; HLN-80H: 7; HLP-40H: 7; HLP-60H: 9; HLP-80H: 7; CEN-60: 22; CEN-75: 22; CEN-100: 22; CLG-60: 23; CLG-100: 13.
Driver-count table, part 7 CLG-150: 8; ELG-75: 10; ELG-100: 8; ELG-150: 8; ELG-75-C: 10; ELG-100-C: 13; ELG-150-C: 8; HBG-100: 8; HBG-160: 8; HBG-240: 7; HBG-60: 18; HLG-40H: 16; HLG-60H: 9; HLG-80H: 7; HLG-100H: 8.
Driver-count table, part 8 HLG-120H: 8; HLG-150H: 8; HLG-185H: 8; HLG-240H: 5; HLG-320H: 6; HLG-600H: 3; HLG-60H-C: 8; HLG-80H-C: 8; HLG-120H-C: 10; HLG-185H-C: 9; HLG-240H-C: 7; HLG-320H-C: 6; HSG-70: 9; HVG-65: 20; HVG-100: 8.
Driver-count table, part 9 HVG-150: 8; HVG-240: 5; HVG-320: 4; HVGC-65: 20; HVGC-100: 8; HVGC-150: 8; HVGC-240: 5; HVGC-320: 4.

Environment, mounting and wiring

Parameter Details
Operating conditions −30°C to +45°C, climatic class 3K5; 10–95% RH, non-condensing.
Storage temperature −35°C to +70°C.
Protection classification Class II according to EN 61140; overvoltage category III and pollution degree 2 according to EN 60664-1; IP20 according to EN 60529.
Dimensions 72 × 90 × 57 mm (W × H × D); 4 modular units wide, case KAA. General mechanical tolerance ±1 mm.
DIN rail 35 mm mounting rail according to EN 60715; TS35/7.5 or TS35/15 as drawn.
Screw-terminal wire 0.5–4.0 mm² solid core or 0.5–2.5 mm² finely stranded wire.
KNX bus terminal 0.8 mm-diameter solid-core wire. Connect the marked KNX+ and KNX− terminals; the drawing uses red for + and black for −.
Load wiring Switch the supply line through the selected relay contact and connect the load neutral as shown. Apply the load’s protective-earth requirements separately. For shutter motors, use the paired direction outputs and the motor manufacturer’s wiring instructions.
Unit mass 247 g per unit; packing reference: 48 pieces / 12.53 kg / 1.02 CUFT.

Standards and reliability

Parameter Details
Safety model KAA-4R4V-10S
Safety standards BS EN/EN 50491-3; BS EN/EN 60669-1, -2-1 and -2-5; EAC TP TC 004. The catalog identifies a Notified Body test report for the marked tests.
EMC emissions and immunity BS EN/EN 50491-5-1, -5-2 and -5-3; BS EN/EN 50090-2-2; BS EN/EN 60669-2-1 and -2-5; BS EN/EN 63044-5-1, -5-2 and -5-3; EAC TP TC 020.
Withstand voltage Between switching and SELV control circuits: 3.5 kVAC.
MTBF reference 686,900 hours minimum per Telcordia SR-332; 302,300 hours minimum per MIL-HDBK-217F at 25°C. Calculated reliability references, not guaranteed service life.
Specification conditions Unless otherwise stated, parameters are measured at 230 VAC input, rated load and 25°C ambient temperature.
Manufacturer warranty reference The catalog states a 3-year manufacturer warranty, subject to its applicable terms.

Manufacturer installation instructions

Parameter Details
Terminal torque discrepancy The current catalogue states 0.8 Nm, while the instruction manual recommends 5 kgf-cm (4.4 lb-in) at the screw terminals. These values differ. Confirm the instructions for the supplied hardware revision with MEAN WELL before tightening.
KNX terminal and cable layout Use 0.6-0.8 mm solid-wire diameter at the KNX bus terminal and strip 5 mm. The manual lists 350 m maximum from the bus supply to the furthest device, 700 m between devices and 1000 m total bus-line segments; the stated maximum 256 devices remains subject to actual system power and topology.
Secure commissioning For KNX Data Secure, use ETS5 version 5.5.0 or later, the device-specific FDSK from its label and the required project security configuration. The manual also allows unsecured operation when deliberately configured; secure capability alone does not mean the installed system is operating securely.
Relay and dimming terminal preparation The manual specifies 0.5-4.0 mm2 solid or 0.5-2.5 mm2 stranded conductors (12-26 AWG), stripped 6.5 mm, for the relay and dimming screw terminals, with a 3 mm slotted screwdriver. Confirm the applicable terminal torque separately.
Passive dimming interface The DC 0(1)-10 V dimming outputs are passive. Use the appropriate wiring diagram for a compatible 1-10 V or 0-10 V LED driver. A non-dimmable driver can use relay switching only; a shutter motor requires its separate relay wiring arrangement.

MEAN WELL KAA-4R4V-S series: 4-channel KNX actuator and dimmer - KAA-4R4V-10S

Product form

KAA-4R4V-10S — 4-channel KNX actuator and dimmer MEAN WELL KAA-4R4V-10S combines four independent latching relays with four passive 0(1)–10 V... Read more

$364.71 Incl. VAT

    • Guaranteed secure & safe checkout.

      shop pay

    Description

    KAA-4R4V-10S — 4-channel KNX actuator and dimmer

    MEAN WELL KAA-4R4V-10S combines four independent latching relays with four passive 0(1)–10 V current-sinking dimming channels. It is powered from the KNX bus and supports KNX Data Secure, linear or logarithmic dimming, panel operation, timers and scenes.

    Download MEAN WELL KAA-4R4V-S Datasheet (PDF)
    Download MEAN WELL KAA-4R4V-S Instruction Manual (PDF)

    KAA-4R4V-S family: combined catalog pages 29–38, dated 2024-10-16. Use the correct current-rating column for this exact ordering code.

    Model and control functions

    Parameter Details
    Model identity Manufacturer ordering code: KAA-4R4V-10S.
    Supply method Powered by the EIB/KNX bus; no additional power supply is required.
    Relay arrangement Four independent latching relays with four dimming-control channels. Select the required switching, dimming or shutter application in ETS.
    Rated channel selection 10 A per channel. Observe the load-category, total-current and inrush limits below.
    Configuration and manual operation Configure the application with ETS. Panel buttons provide manual operation and status indication. Time and scene functions are programmable.
    KNX Data Secure The device certificate attached to the unit is required for the first secure configuration. After commissioning, remove it from the device as recommended and store it securely. Use a compatible application database and specialist KNX commissioning knowledge.
    Dimming interface Four DC 0(1)–10 V passive current-sinking outputs for compatible LED drivers or electronic ballasts. This is a control interface, not an LED load power supply.
    Dimming response Linear or logarithmic dimming curves are selectable in ETS. Each channel has a green status LED.
    Communication functions Central manual enable, switching, absolute dimming and operation status; channel switching/status, relative and absolute dimming, scenes, automatic functions, blocking and staircase-light functions. The communication-object table also provides prewarning and permanent ON; use the application database for the applicable objects and flags.

    Electrical and switching ratings

    Parameter Details
    KNX bus supply 21–31 VDC.
    Bus current and power Below 14 mA; below 250 mW.
    Relay output rating 230 VAC, 50 Hz; 10 A ohmic load per relay. Each relay is independent and potential-free.
    Capacitive load 220 µF; the catalog identifies a Notified Body test report.
    Maximum inrush current 400 A for a maximum 200 µs, or 80 A for a maximum 20 ms.
    Load categories EN 60947-4-1: AC1 (cos φ = 0.8) 10 A; AC5a (cos φ = 0.45) 8 A; AC5b 10 A.
    Maximum total current 40 A for the actuator; the per-channel rating does not override this aggregate limit.
    Service life Mechanical: more than 10⁶ cycles. Electrical endurance EN 60669-1 section 19.1: 4 × 10⁴ cycles; fluorescent lamp (AX), section 19.2: 10⁴ cycles. The specified electrical tests have a Notified Body test report.
    Shutter outputs Two paired shutter outputs.
    Dimming output limit Four passive 0–10 V control outputs, maximum 50 mA sinking current per output.
    Dimming cable length Up to 100 m at full control load with 1.5 mm² cable.
    Control-device quantity Up to 500 drivers per dimming-control channel only when each driver sources 0.1 mA. Actual allowable quantity also depends on the installation, including total cable length. This is separate from relay switching capacity.

    Load and driver selection

    Parameter Details
    Maximum load per channel Resistive load: 2300 W; incandescent lamps: 2300 W; 230 V halogen lamps: 2300 W; halogen electronic transformers: 1300 W; fluorescent lamps without compensation: 2000 W; parallel-compensated fluorescent lamps: 1200 W; maximum 15 electronic transformers; shutter motor: 600 W.
    LED-driver quantity The following catalog values are maximum numbers of MEAN WELL LED power supplies per relay channel at 230 V. Respect the exact driver series, load, inrush and total-current limits; these are not counts for mixed-driver combinations.
    Driver-count table, part 1 APC-8: 22; APC-12: 11; APC-16: 18; APC-25: 11; APC-35: 11; APC-8E: 22; APC-12E: 18; APC-16E: 15; APV-8: 22; APV-12: 11; APV-16: 18; APV-25: 11; APV-35: 11; APV-8E: 22; APV-12E: 18.
    Driver-count table, part 2 APV-16E: 15; LCM-25: 25; LCM-40: 25; LCM-60: 25; LCM-25DA: 25; LCM-40DA: 25; LCM-60DA: 25; LPC-20: 11; LPC-35: 9; LPC-60: 8; LPC-100: 7; LPC-150: 5; LPF-16: 18; LPF-25: 16; LPF-40: 16.
    Driver-count table, part 3 LPF-60: 9; LPF-90: 7; LPF-16D: 18; LPF-25D: 16; LPF-40D: 16; LPF-60D: 9; LPF-90D: 7; LPH-18: 16; LPHC-18: 16; LPV-20: 11; LPV-35: 9; LPV-60: 8; LPV-100: 7; LPV-150: 8; NPF-40: 10.
    Driver-count table, part 4 NPF-60: 10; NPF-90: 8; NPF-120: 8; NPF-40D: 10; NPF-60D: 10; NPF-90D: 8; NPF-120D: 8; PCD-16B: 80; PCD-25B: 53; PCD-40B: 45; PCD-60B: 26; PLC-30: 23; PLC-45: 23; PLC-60: 23; PLC-100: 13.
    Driver-count table, part 5 PLD-16B: 40; PLD-25: 32; PLD-40B: 32; PLD-60B: 32; PLM-12: 53; PLM-25: 53; PLM-40: 53; PLN-20: 23; PLN-30: 23; PLN-45: 23; PLN-60: 23; PLN-100: 13; PLP-30: 32; PLP-45: 27; PLP-60: 23.
    Driver-count table, part 6 PWM-40: 10; PWM-60: 10; PWM-90: 8; PWM-120: 8; HLN-40H: 10; HLN-60H: 9; HLN-80H: 7; HLP-40H: 7; HLP-60H: 9; HLP-80H: 7; CEN-60: 22; CEN-75: 22; CEN-100: 22; CLG-60: 23; CLG-100: 13.
    Driver-count table, part 7 CLG-150: 8; ELG-75: 10; ELG-100: 8; ELG-150: 8; ELG-75-C: 10; ELG-100-C: 13; ELG-150-C: 8; HBG-100: 8; HBG-160: 8; HBG-240: 7; HBG-60: 18; HLG-40H: 16; HLG-60H: 9; HLG-80H: 7; HLG-100H: 8.
    Driver-count table, part 8 HLG-120H: 8; HLG-150H: 8; HLG-185H: 8; HLG-240H: 5; HLG-320H: 6; HLG-600H: 3; HLG-60H-C: 8; HLG-80H-C: 8; HLG-120H-C: 10; HLG-185H-C: 9; HLG-240H-C: 7; HLG-320H-C: 6; HSG-70: 9; HVG-65: 20; HVG-100: 8.
    Driver-count table, part 9 HVG-150: 8; HVG-240: 5; HVG-320: 4; HVGC-65: 20; HVGC-100: 8; HVGC-150: 8; HVGC-240: 5; HVGC-320: 4.

    Environment, mounting and wiring

    Parameter Details
    Operating conditions −30°C to +45°C, climatic class 3K5; 10–95% RH, non-condensing.
    Storage temperature −35°C to +70°C.
    Protection classification Class II according to EN 61140; overvoltage category III and pollution degree 2 according to EN 60664-1; IP20 according to EN 60529.
    Dimensions 72 × 90 × 57 mm (W × H × D); 4 modular units wide, case KAA. General mechanical tolerance ±1 mm.
    DIN rail 35 mm mounting rail according to EN 60715; TS35/7.5 or TS35/15 as drawn.
    Screw-terminal wire 0.5–4.0 mm² solid core or 0.5–2.5 mm² finely stranded wire.
    KNX bus terminal 0.8 mm-diameter solid-core wire. Connect the marked KNX+ and KNX− terminals; the drawing uses red for + and black for −.
    Load wiring Switch the supply line through the selected relay contact and connect the load neutral as shown. Apply the load’s protective-earth requirements separately. For shutter motors, use the paired direction outputs and the motor manufacturer’s wiring instructions.
    Unit mass 247 g per unit; packing reference: 48 pieces / 12.53 kg / 1.02 CUFT.

    Standards and reliability

    Parameter Details
    Safety model KAA-4R4V-10S
    Safety standards BS EN/EN 50491-3; BS EN/EN 60669-1, -2-1 and -2-5; EAC TP TC 004. The catalog identifies a Notified Body test report for the marked tests.
    EMC emissions and immunity BS EN/EN 50491-5-1, -5-2 and -5-3; BS EN/EN 50090-2-2; BS EN/EN 60669-2-1 and -2-5; BS EN/EN 63044-5-1, -5-2 and -5-3; EAC TP TC 020.
    Withstand voltage Between switching and SELV control circuits: 3.5 kVAC.
    MTBF reference 686,900 hours minimum per Telcordia SR-332; 302,300 hours minimum per MIL-HDBK-217F at 25°C. Calculated reliability references, not guaranteed service life.
    Specification conditions Unless otherwise stated, parameters are measured at 230 VAC input, rated load and 25°C ambient temperature.
    Manufacturer warranty reference The catalog states a 3-year manufacturer warranty, subject to its applicable terms.

    Manufacturer installation instructions

    Parameter Details
    Terminal torque discrepancy The current catalogue states 0.8 Nm, while the instruction manual recommends 5 kgf-cm (4.4 lb-in) at the screw terminals. These values differ. Confirm the instructions for the supplied hardware revision with MEAN WELL before tightening.
    KNX terminal and cable layout Use 0.6-0.8 mm solid-wire diameter at the KNX bus terminal and strip 5 mm. The manual lists 350 m maximum from the bus supply to the furthest device, 700 m between devices and 1000 m total bus-line segments; the stated maximum 256 devices remains subject to actual system power and topology.
    Secure commissioning For KNX Data Secure, use ETS5 version 5.5.0 or later, the device-specific FDSK from its label and the required project security configuration. The manual also allows unsecured operation when deliberately configured; secure capability alone does not mean the installed system is operating securely.
    Relay and dimming terminal preparation The manual specifies 0.5-4.0 mm2 solid or 0.5-2.5 mm2 stranded conductors (12-26 AWG), stripped 6.5 mm, for the relay and dimming screw terminals, with a 3 mm slotted screwdriver. Confirm the applicable terminal torque separately.
    Passive dimming interface The DC 0(1)-10 V dimming outputs are passive. Use the appropriate wiring diagram for a compatible 1-10 V or 0-10 V LED driver. A non-dimmable driver can use relay switching only; a shutter motor requires its separate relay wiring arrangement.