MEAN WELL NCP-3200 series: Programmable Rack Power Supply and Battery Charger - NCP-3200-24CAN

Description

MEAN WELL NCP-3200-24CAN is a 1U rack-mounted power module with 24 V factory output, 133 A factory current and 3192 W maximum rated power. It also supports selectable two- or three-stage battery charging and fits the DHP-1UT-B rack. This complete ordering code selects CANBus communication.

Product Datasheet

Download MEAN WELL NCP-3200 Datasheet (PDF)

The NCP-3200 section is on PDF pages 23, 24, 25, 26, 27, 28, 29, 30, 31, 32. Refer to the complete mechanical drawings and notes when planning installation.

Power Supply Ratings

DC output voltage 24 V
Rated output current 133 A
Maximum output power 3192 W
Output current range 0–133 A
Voltage adjustment range 23.5–30 V
Ripple and noise, maximum 300 mVp-p
Voltage tolerance ±1.0%
Line / load regulation ±0.5% / ±0.5%
Communication option CANBus

Power supply operation is the factory default. Voltage, current, power, input and thermal limits apply together; the separate maximum values are not available simultaneously at every setting.

Ripple is measured at 20 MHz using a 12-inch twisted pair terminated with parallel 0.1 µF and 47 µF capacitors. Light-load ripple can increase under variable load or parallel operation and returns to its normal level above 5% load. PV adjustment can also increase ripple under some conditions. Voltage tolerance includes setup, line and load effects.

Input and Timing

AC input 90–264 VAC
DC input 127–400 VDC
Input frequency 47–63 Hz
Typical AC current 17 A at 230 VAC
Typical power factor 0.97 at 230 VAC, full load
Typical PSU efficiency 93.5% at 75% load
Cold-start inrush 55 A at 230 VAC
Leakage current <2 mA at 230 VAC
Setup / rise time 1500 ms / 60 ms at 230 VAC, full load
Typical hold-up 16 ms at 230 VAC, 70% load; 8 ms at full load

Unless otherwise specified, values use 230 VAC input, rated load and 25°C ambient. The block diagram shows active inrush limiting, PFC at 110 kHz and PWM at 90 kHz.

Cooling and Derating

Cooling Built-in DC fans with intelligent speed control
Horizontal thermal curve 80% at −30°C, 100% from −20 to +50°C, then 50% at +70°C
Cold operating region −30 to −20°C: 230 VAC input only
AC-input load curve 50% at 90 VAC, increasing to 100% at 180 VAC; full load through 264 VAC, at 60 Hz
90 VAC operating point 1596 W / 66.5 A

Apply the AC and temperature derating simultaneously. The 48 V efficiency-versus-load graph is measured at 230 VAC; it is not an efficiency guarantee for every model and load. Keep the intake and exhaust unobstructed.

Protection

PSU overload 105–115% of rated current; constant-current limiting, shutdown after 5 seconds, re-power to recover
Overvoltage 31.5–37.5 V; output shutdown, re-power to recover
Overtemperature Output shutdown; automatic recovery after cooling
Low output in PSU control Output below 80% of Vset for 5 seconds: shutdown; re-power to recover

Short-circuit protection is listed as a series feature. The specified limiting, power and recovery conditions must be observed; no separate undocumented short-circuit timing is assumed.

Selectable Battery Charging

Default boost charge voltage 28.8 V
Default float charge voltage 27.6 V
Default charging current 110 A
Suggested battery capacity 330–1000 Ah
Typical charger efficiency 93%
Typical battery leakage <1.5 mA
Preset gel boost / float 28 / 27.2 V
Preset flooded boost / float 28.4 / 26.8 V
Preset AGM boost / float 29 / 27 V

Select charger mode through the fitted communication interface or the separately available SBP-001 programmer. The charging-curve default is three-stage CC/CV/float; two-stage CC/CV operation is also supported. At the indicated 10% of CC transition, the three-stage curve enters float, while the two-stage graph shows battery-full completion. Two-stage presets use the same boost values without a float stage.

Default and preset curves retain the listed CC setting. Charging parameters and stage timeouts can be programmed through communication; SBP-001 programming requires a personal computer. The catalogue lists flooded, gel and AGM lead-acid batteries and lithium-ion iron/manganese types. Confirm the actual battery chemistry, voltage and maximum permitted charging current with the battery manufacturer before choosing a curve; the Ah range is a recommendation, not universal battery compatibility.

Output Voltage and Current Programming

PV adjustment 50–125% of the graph’s nominal reference voltage
PC adjustment 20–100% of rated current
PV connection CN1 pin 25 to CN1 pin 26 (−V signal)
PC connection CN1 pin 17 to CN1 pin 26 (−V signal)

PV applies to power supply operation. The graph uses 24/48 V as the 100% voltage reference. Below 0.4 V control input the output is at its factory setting; 0.4–1 V selects 50%, then the curve rises nonlinearly toward 125% at approximately 4.7 V control input. Use the published curve rather than assuming a linear conversion over the entire control range.

Available output current changes with the voltage setting: 80% from 50–90% output voltage, rising to 100% at 95%, then remaining at 100% through 100% voltage. Above that, current decreases to 80% at 125% voltage (30 V or 60 V). The graph’s 100% current reference is 133/67 A. Always keep output within the maximum power limit.

For PC, 0.4–1 V control input corresponds to 20% current; the nonlinear rising region reaches 100% at 4.7 V and remains at 100% to 5 V. The plot below 0.4 V is an approximately 110% limiting region, not an additional rated operating range. Very low constant-current settings can increase ripple. Output below 80% of Vset for 5 seconds causes shutdown; re-power to recover.

Remote and Local Sense

Remote sense is available only for the 24 V / 48 V models in power supply mode. Connect CN1 pin 28 (+S) to load positive and pin 27 (−S) to load negative using a twisted pair; compensation is up to 0.5 V.

When remote sense is not used, connect pin 28 (+S) to pin 29 (+V signal) and pin 27 (−S) to pin 26 (−V signal). Signal pins are not power terminals and must not carry the load current.

Connector, Control and Auxiliary Outputs

CN1 connector C27309-10749-Y
Mating housing C27209-10749-Y
Pins 1, 2 / 3, 4 −V output / +V output
Pin 5 +12V-AUX: 10.8–13.2 V, 0.8 A maximum
Pin 6 +5V-AUX: 4.5–5.5 V, 0.3 A maximum
Pin 7 GND-AUX; isolated signal return
Pin 8 / pin 9 AC-OK / T-ALARM
Pins 10, 24 NC; reserved
Pin 11 / pin 12 CANL / CANH
Pin 13 Remote ON-OFF
Pin 14 DC-OK
Pins 15, 16 DA, DB: differential parallel-control signals
Pin 17 PC
Pins 18, 19, 20, 21 A2, A3, A4, A5: rack-system addressing
Pins 22, 23 A0, A1: module addressing
Pin 25 PV
Pin 26 −V signal; control reference, not a load terminal
Pins 27, 28, 29 −S, +S, +V signal; 24 V / 48 V PSU sense only
Pins 30, 31, 32 FG, AC/N, AC/L

Use the rear-view orientation and complete connector assignment in the mechanical drawing. Ask MEAN WELL for the correct mating assembly; the catalogue identifies the housing but does not provide a separate full crimp-contact ordering code.

Remote ON-OFF is between pin 13 and pin 6 (+5V-AUX): short / 4.5–5.5 V means ON; open / −0.5 to +0.5 V means OFF. Maximum input is 5.5 V. The auxiliary outputs have OR-ing diodes and are not switched by this remote control; both use GND-AUX pin 7.

Auxiliary ratings are 5 V at 0.3 A, ±10%, 150 mVp-p ripple and 12 V at 0.8 A, ±10%, 450 mVp-p ripple. PV, PC, parallel and address signals are non-isolated and reference −V signal; communication, remote and alarm signals reference the isolated GND-AUX.

Communication, Alarms and Indicators

The CAN suffix selects CAN 2.0B. The catalogue prints a maximum bus speed of 250 KHz; use the protocol manual for bus setup and message details.

Alarm outputs are isolated TTL, referenced to GND-AUX, output-only and rated 10 mA maximum. High is 3.5–5.5 V and low is −0.5 to +0.5 V. AC-OK is high at input ≥87 Vrms and low at ≤75 Vrms. T-ALARM is high for temperature alarm or fan failure, and low during normal operation.

In power supply mode, DC-OK is high when output is ≤77% ±5%, and low when output is ≥80% ±5%. In charger mode the thresholds are ≤66% ±5% high and ≥67% ±5% low; DC-OK is associated with battery-low protection.

The status LED is green during normal power supply operation and steady red for abnormal protection/fan status. Flashing red at an internal temperature of 60°C signals an alarm while normal operation continues without entering OTP. In charger mode, orange identifies CC/CV charging, green identifies float, and red also covers charging timeout. The two-stage graph identifies green at battery full.

Rack Operation and Accessories

Compatible rack DHP-1UT-B
Parallel arrangement Up to four identical modules per rack; up to ten racks / forty modules
Controller series CMU2; select the compatible controller configuration
Charging programmer SBP-001 with a personal computer

A DHP-1UT-B rack accepts identical 24 V modules or identical 48 V modules; do not mix unlike voltage/current models in one parallel group.

For parallel racks, set output-voltage differences to less than 0.2 V, join DA, DB and −V control lines as shown, and configure the parallel system before connecting the load. Use the matching rack manual and protocol arrangement. A 10% reduction in total output current is recommended to avoid unequal limiting caused by component tolerances; the maximum module count is not a promise of unrestricted full-power operation.

The module supports hot swap and built-in OR-ing FET or diode isolation. Racks, programming equipment and controller configurations are separate selection items; confirm the actual supply scope.

Mechanical Installation

Dimensions, L × W × H 325.8 × 107 × 41 mm
Catalogue unit weight 2300 g; catalogue packing reference per unit, not measured net or shipping weight
Case drawing 294B; general dimensional tolerance ±0.5 mm
Mounting details Two M4 L=5 positions per side; two Ø2.8 holes per side
Body and projection details 276 mm marked mounting-centre spacing; 10.5 mm maximum connector projection; handle projects 29.3 mm

Follow the drawing for the separate 127 mm and 137 mm mounting-envelope dimensions, rather than treating them as body width. The front contains the handle, status indicator and controlled fans; airflow arrows point from the front toward the connector end. The built-in adjustment is marked SVR. The series describes power density up to 37 W/in³; this is a series upper claim.

Environment and Reliability

Operating ambient −30 to +70°C, subject to input and thermal derating
Operating humidity 20–90% RH, non-condensing
Storage −40 to +85°C; 10–95% RH, non-condensing
Temperature coefficient ±0.03%/°C from 0 to 50°C
Vibration 10–500 Hz, 2G; 10 minutes/cycle, 60 minutes each along X, Y and Z
Minimum calculated MTBF 510.5 thousand hours, Telcordia SR-332; 45.8 thousand hours, MIL-HDBK-217F at 25°C
Manufacturer warranty 5 years

For fan-cooled operation above 2000 m, reduce permissible ambient temperature by 5°C per additional 1000 m. This derating note does not establish a maximum operating altitude.

Safety and EMC

Dielectric withstand Input/output: 3 kVAC; input/FG: 2 kVAC; output/FG: 1.5 kVAC
Insulation resistance 100 MΩ between input/output, input/FG and output/FG; 500 VDC, 25°C, 70% RH
Conducted / radiated emissions BS EN/EN 55032 (CISPR32): Class B conducted / Class A radiated
Harmonic current / voltage flicker BS EN/EN 61000-3-2 Class A / BS EN/EN 61000-3-3

The power supply specification lists UL 62368-1, CSA C22.2 No. 62368-1, TUV BS EN/EN 62368-1 and EAC TP TC 004 approvals, with design referring to AS/NZS 62368.1. RCM is voluntary under the referenced IEC/AS/NZS requirements. These component qualifications do not certify the completed installation. The power supply design refers to SEMI F47 at 200 VAC.

Immunity references BS EN/EN 55024 and 61000-6-2, with tests under 61000-4-2/-3/-4/-5/-6/-8/-11: ESD 8 kV air and 4 kV contact; radiated RF, EFT/burst and conducted RF Level 3; surge 2 kV line-to-line and 4 kV line-to-earth; magnetic field Level 4. Voltage dips are >95% for 0.5 period and 30% for 25 periods; interruptions are >95% for 250 periods.

The catalogue EMC arrangement mounts the component on a 600 × 900 mm metal plate, 1 mm thick. Reconfirm compliance in the final equipment.

MEAN WELL NCP-3200 series: Programmable Rack Power Supply and Battery Charger - NCP-3200-24CAN

Product form

MEAN WELL NCP-3200-24CAN is a 1U rack-mounted power module with 24 V factory output, 133 A factory current and 3192... Read more

$2,457.39 Incl. VAT

    • Guaranteed secure & safe checkout.

      shop pay

    Description

    MEAN WELL NCP-3200-24CAN is a 1U rack-mounted power module with 24 V factory output, 133 A factory current and 3192 W maximum rated power. It also supports selectable two- or three-stage battery charging and fits the DHP-1UT-B rack. This complete ordering code selects CANBus communication.

    Product Datasheet

    Download MEAN WELL NCP-3200 Datasheet (PDF)

    The NCP-3200 section is on PDF pages 23, 24, 25, 26, 27, 28, 29, 30, 31, 32. Refer to the complete mechanical drawings and notes when planning installation.

    Power Supply Ratings

    DC output voltage 24 V
    Rated output current 133 A
    Maximum output power 3192 W
    Output current range 0–133 A
    Voltage adjustment range 23.5–30 V
    Ripple and noise, maximum 300 mVp-p
    Voltage tolerance ±1.0%
    Line / load regulation ±0.5% / ±0.5%
    Communication option CANBus

    Power supply operation is the factory default. Voltage, current, power, input and thermal limits apply together; the separate maximum values are not available simultaneously at every setting.

    Ripple is measured at 20 MHz using a 12-inch twisted pair terminated with parallel 0.1 µF and 47 µF capacitors. Light-load ripple can increase under variable load or parallel operation and returns to its normal level above 5% load. PV adjustment can also increase ripple under some conditions. Voltage tolerance includes setup, line and load effects.

    Input and Timing

    AC input 90–264 VAC
    DC input 127–400 VDC
    Input frequency 47–63 Hz
    Typical AC current 17 A at 230 VAC
    Typical power factor 0.97 at 230 VAC, full load
    Typical PSU efficiency 93.5% at 75% load
    Cold-start inrush 55 A at 230 VAC
    Leakage current <2 mA at 230 VAC
    Setup / rise time 1500 ms / 60 ms at 230 VAC, full load
    Typical hold-up 16 ms at 230 VAC, 70% load; 8 ms at full load

    Unless otherwise specified, values use 230 VAC input, rated load and 25°C ambient. The block diagram shows active inrush limiting, PFC at 110 kHz and PWM at 90 kHz.

    Cooling and Derating

    Cooling Built-in DC fans with intelligent speed control
    Horizontal thermal curve 80% at −30°C, 100% from −20 to +50°C, then 50% at +70°C
    Cold operating region −30 to −20°C: 230 VAC input only
    AC-input load curve 50% at 90 VAC, increasing to 100% at 180 VAC; full load through 264 VAC, at 60 Hz
    90 VAC operating point 1596 W / 66.5 A

    Apply the AC and temperature derating simultaneously. The 48 V efficiency-versus-load graph is measured at 230 VAC; it is not an efficiency guarantee for every model and load. Keep the intake and exhaust unobstructed.

    Protection

    PSU overload 105–115% of rated current; constant-current limiting, shutdown after 5 seconds, re-power to recover
    Overvoltage 31.5–37.5 V; output shutdown, re-power to recover
    Overtemperature Output shutdown; automatic recovery after cooling
    Low output in PSU control Output below 80% of Vset for 5 seconds: shutdown; re-power to recover

    Short-circuit protection is listed as a series feature. The specified limiting, power and recovery conditions must be observed; no separate undocumented short-circuit timing is assumed.

    Selectable Battery Charging

    Default boost charge voltage 28.8 V
    Default float charge voltage 27.6 V
    Default charging current 110 A
    Suggested battery capacity 330–1000 Ah
    Typical charger efficiency 93%
    Typical battery leakage <1.5 mA
    Preset gel boost / float 28 / 27.2 V
    Preset flooded boost / float 28.4 / 26.8 V
    Preset AGM boost / float 29 / 27 V

    Select charger mode through the fitted communication interface or the separately available SBP-001 programmer. The charging-curve default is three-stage CC/CV/float; two-stage CC/CV operation is also supported. At the indicated 10% of CC transition, the three-stage curve enters float, while the two-stage graph shows battery-full completion. Two-stage presets use the same boost values without a float stage.

    Default and preset curves retain the listed CC setting. Charging parameters and stage timeouts can be programmed through communication; SBP-001 programming requires a personal computer. The catalogue lists flooded, gel and AGM lead-acid batteries and lithium-ion iron/manganese types. Confirm the actual battery chemistry, voltage and maximum permitted charging current with the battery manufacturer before choosing a curve; the Ah range is a recommendation, not universal battery compatibility.

    Output Voltage and Current Programming

    PV adjustment 50–125% of the graph’s nominal reference voltage
    PC adjustment 20–100% of rated current
    PV connection CN1 pin 25 to CN1 pin 26 (−V signal)
    PC connection CN1 pin 17 to CN1 pin 26 (−V signal)

    PV applies to power supply operation. The graph uses 24/48 V as the 100% voltage reference. Below 0.4 V control input the output is at its factory setting; 0.4–1 V selects 50%, then the curve rises nonlinearly toward 125% at approximately 4.7 V control input. Use the published curve rather than assuming a linear conversion over the entire control range.

    Available output current changes with the voltage setting: 80% from 50–90% output voltage, rising to 100% at 95%, then remaining at 100% through 100% voltage. Above that, current decreases to 80% at 125% voltage (30 V or 60 V). The graph’s 100% current reference is 133/67 A. Always keep output within the maximum power limit.

    For PC, 0.4–1 V control input corresponds to 20% current; the nonlinear rising region reaches 100% at 4.7 V and remains at 100% to 5 V. The plot below 0.4 V is an approximately 110% limiting region, not an additional rated operating range. Very low constant-current settings can increase ripple. Output below 80% of Vset for 5 seconds causes shutdown; re-power to recover.

    Remote and Local Sense

    Remote sense is available only for the 24 V / 48 V models in power supply mode. Connect CN1 pin 28 (+S) to load positive and pin 27 (−S) to load negative using a twisted pair; compensation is up to 0.5 V.

    When remote sense is not used, connect pin 28 (+S) to pin 29 (+V signal) and pin 27 (−S) to pin 26 (−V signal). Signal pins are not power terminals and must not carry the load current.

    Connector, Control and Auxiliary Outputs

    CN1 connector C27309-10749-Y
    Mating housing C27209-10749-Y
    Pins 1, 2 / 3, 4 −V output / +V output
    Pin 5 +12V-AUX: 10.8–13.2 V, 0.8 A maximum
    Pin 6 +5V-AUX: 4.5–5.5 V, 0.3 A maximum
    Pin 7 GND-AUX; isolated signal return
    Pin 8 / pin 9 AC-OK / T-ALARM
    Pins 10, 24 NC; reserved
    Pin 11 / pin 12 CANL / CANH
    Pin 13 Remote ON-OFF
    Pin 14 DC-OK
    Pins 15, 16 DA, DB: differential parallel-control signals
    Pin 17 PC
    Pins 18, 19, 20, 21 A2, A3, A4, A5: rack-system addressing
    Pins 22, 23 A0, A1: module addressing
    Pin 25 PV
    Pin 26 −V signal; control reference, not a load terminal
    Pins 27, 28, 29 −S, +S, +V signal; 24 V / 48 V PSU sense only
    Pins 30, 31, 32 FG, AC/N, AC/L

    Use the rear-view orientation and complete connector assignment in the mechanical drawing. Ask MEAN WELL for the correct mating assembly; the catalogue identifies the housing but does not provide a separate full crimp-contact ordering code.

    Remote ON-OFF is between pin 13 and pin 6 (+5V-AUX): short / 4.5–5.5 V means ON; open / −0.5 to +0.5 V means OFF. Maximum input is 5.5 V. The auxiliary outputs have OR-ing diodes and are not switched by this remote control; both use GND-AUX pin 7.

    Auxiliary ratings are 5 V at 0.3 A, ±10%, 150 mVp-p ripple and 12 V at 0.8 A, ±10%, 450 mVp-p ripple. PV, PC, parallel and address signals are non-isolated and reference −V signal; communication, remote and alarm signals reference the isolated GND-AUX.

    Communication, Alarms and Indicators

    The CAN suffix selects CAN 2.0B. The catalogue prints a maximum bus speed of 250 KHz; use the protocol manual for bus setup and message details.

    Alarm outputs are isolated TTL, referenced to GND-AUX, output-only and rated 10 mA maximum. High is 3.5–5.5 V and low is −0.5 to +0.5 V. AC-OK is high at input ≥87 Vrms and low at ≤75 Vrms. T-ALARM is high for temperature alarm or fan failure, and low during normal operation.

    In power supply mode, DC-OK is high when output is ≤77% ±5%, and low when output is ≥80% ±5%. In charger mode the thresholds are ≤66% ±5% high and ≥67% ±5% low; DC-OK is associated with battery-low protection.

    The status LED is green during normal power supply operation and steady red for abnormal protection/fan status. Flashing red at an internal temperature of 60°C signals an alarm while normal operation continues without entering OTP. In charger mode, orange identifies CC/CV charging, green identifies float, and red also covers charging timeout. The two-stage graph identifies green at battery full.

    Rack Operation and Accessories

    Compatible rack DHP-1UT-B
    Parallel arrangement Up to four identical modules per rack; up to ten racks / forty modules
    Controller series CMU2; select the compatible controller configuration
    Charging programmer SBP-001 with a personal computer

    A DHP-1UT-B rack accepts identical 24 V modules or identical 48 V modules; do not mix unlike voltage/current models in one parallel group.

    For parallel racks, set output-voltage differences to less than 0.2 V, join DA, DB and −V control lines as shown, and configure the parallel system before connecting the load. Use the matching rack manual and protocol arrangement. A 10% reduction in total output current is recommended to avoid unequal limiting caused by component tolerances; the maximum module count is not a promise of unrestricted full-power operation.

    The module supports hot swap and built-in OR-ing FET or diode isolation. Racks, programming equipment and controller configurations are separate selection items; confirm the actual supply scope.

    Mechanical Installation

    Dimensions, L × W × H 325.8 × 107 × 41 mm
    Catalogue unit weight 2300 g; catalogue packing reference per unit, not measured net or shipping weight
    Case drawing 294B; general dimensional tolerance ±0.5 mm
    Mounting details Two M4 L=5 positions per side; two Ø2.8 holes per side
    Body and projection details 276 mm marked mounting-centre spacing; 10.5 mm maximum connector projection; handle projects 29.3 mm

    Follow the drawing for the separate 127 mm and 137 mm mounting-envelope dimensions, rather than treating them as body width. The front contains the handle, status indicator and controlled fans; airflow arrows point from the front toward the connector end. The built-in adjustment is marked SVR. The series describes power density up to 37 W/in³; this is a series upper claim.

    Environment and Reliability

    Operating ambient −30 to +70°C, subject to input and thermal derating
    Operating humidity 20–90% RH, non-condensing
    Storage −40 to +85°C; 10–95% RH, non-condensing
    Temperature coefficient ±0.03%/°C from 0 to 50°C
    Vibration 10–500 Hz, 2G; 10 minutes/cycle, 60 minutes each along X, Y and Z
    Minimum calculated MTBF 510.5 thousand hours, Telcordia SR-332; 45.8 thousand hours, MIL-HDBK-217F at 25°C
    Manufacturer warranty 5 years

    For fan-cooled operation above 2000 m, reduce permissible ambient temperature by 5°C per additional 1000 m. This derating note does not establish a maximum operating altitude.

    Safety and EMC

    Dielectric withstand Input/output: 3 kVAC; input/FG: 2 kVAC; output/FG: 1.5 kVAC
    Insulation resistance 100 MΩ between input/output, input/FG and output/FG; 500 VDC, 25°C, 70% RH
    Conducted / radiated emissions BS EN/EN 55032 (CISPR32): Class B conducted / Class A radiated
    Harmonic current / voltage flicker BS EN/EN 61000-3-2 Class A / BS EN/EN 61000-3-3

    The power supply specification lists UL 62368-1, CSA C22.2 No. 62368-1, TUV BS EN/EN 62368-1 and EAC TP TC 004 approvals, with design referring to AS/NZS 62368.1. RCM is voluntary under the referenced IEC/AS/NZS requirements. These component qualifications do not certify the completed installation. The power supply design refers to SEMI F47 at 200 VAC.

    Immunity references BS EN/EN 55024 and 61000-6-2, with tests under 61000-4-2/-3/-4/-5/-6/-8/-11: ESD 8 kV air and 4 kV contact; radiated RF, EFT/burst and conducted RF Level 3; surge 2 kV line-to-line and 4 kV line-to-earth; magnetic field Level 4. Voltage dips are >95% for 0.5 period and 30% for 25 periods; interruptions are >95% for 250 periods.

    The catalogue EMC arrangement mounts the component on a 600 × 900 mm metal plate, 1 mm thick. Reconfirm compliance in the final equipment.