MEAN WELL SDR-240 series: Industrial DIN Rail Power Supply - SDR-240-48

Description

MEAN WELL SDR-240-48 is a single-output industrial DIN rail power supply rated at 48 V DC, 5 A and 240 W. It accepts 88–264 VAC or 124–370 VDC, uses free-air convection and includes active PFC, adjustable output and a DC OK relay. Peak output up to 360 W is limited to three seconds and the operating conditions below.

Product Datasheet

Download MEAN WELL SDR-240 Datasheet (PDF)

The SDR-240 section is on PDF pages 7, 8, 9. Refer to the complete mechanical drawings and notes when planning installation.

Model and Output

Complete model SDR-240-48; SDR-240 catalogue revision 2025-02-17. The final number identifies the nominal 48 V output.
Rated DC output 48 V / 5 A / 240 W; current range 0–5 A.
Peak output 7.5 A / 360 W (150% of rated power), for a maximum of 3 seconds and subject to the peak-loading and derating conditions below.
Voltage adjustment 48–55 V using +V ADJ. Observe the rated current and power limits when adjusting voltage.
Ripple and noise 50 mVp-p maximum, measured at 20 MHz bandwidth with a 12-inch twisted pair terminated by parallel 0.1 µF and 47 µF capacitors.
Voltage tolerance ±1%, including setup tolerance, line regulation and load regulation.
Line / load regulation ±0.5% / ±1.0%, respectively.
Typical efficiency 94% typical at 230 VAC, rated load and 25°C ambient; measured after 30 minutes of burn-in.

Input and Timing

AC / DC input 88–264 VAC or 124–370 VDC; AC frequency 47–63 Hz.
Active PFC / typical power factor Built-in active power-factor correction; typical PF 0.94 at 230 VAC and 0.99 at 115 VAC, at full load.
Typical AC input current 2.6 A at 115 VAC; 1.3 A at 230 VAC.
Typical inrush current 33 A at 115 VAC; 55 A at 230 VAC.
Leakage current Less than 1 mA at 240 VAC.
Setup / rise time 650 / 60 ms at 230 VAC; 1300 / 60 ms at 115 VAC, at full load.
Typical hold-up time 20 ms at both 230 VAC and 115 VAC, at full load.

Unless otherwise stated, specifications are measured at 230 VAC input, rated load and 25°C ambient.

Peak Loading and Derating

Peak-duration limit Up to 360 W for no more than 3 seconds, within the permitted input and temperature conditions. Peak capability is not a continuous power rating.
Temperature curves For vertical mounting, continuous load is 100% from −25 to +60°C, decreasing to 75% at +70°C. The three-second peak curve is 150% through +60°C, decreasing to 112.5% at +70°C.
Input-voltage curve At 60 Hz AC, the graph shows 90% load at 88 VAC, increasing to 100% at 100 VAC and remaining at 100% through 264 VAC.
Cooling / orientation Free-air convection; use vertical mounting for the published temperature-derating curves. Keep the ventilation path unobstructed.

The page 9 peak-loading diagrams show two examples: 240 W for 100 seconds followed by 360 W for 3 seconds, or 120 W for 10 seconds followed by 360 W for 3 seconds. The marked 100-second and 10-second durations are the lower-load intervals, not the complete cycle periods. These examples do not establish an unrestricted duty cycle for other load patterns.

Apply the input and temperature restrictions together; use the more restrictive allowable load. See PDF page 9 for the full curves.

Protection and DC OK Monitoring

Short circuit / overload The catalogue lists short-circuit protection. At 110–150% of rated output power, overload operation lasting more than 3 seconds is followed by output shutdown with automatic recovery.
Above 150% rated power Constant-current limiting with automatic recovery within 2 seconds; operation beyond 2 seconds may cause output shutdown.
Overvoltage 56–65 V; output shutdown, with automatic recovery.
Overtemperature 95±5°C at TSW on the heatsink of the power switch; output shuts down and recovers automatically after cooling. This is an internal sensing temperature, not an ambient operating limit.
DC OK relay states Contact closed: PSU turns on / DC OK. Contact open: PSU turns off / DC Fail.
DC OK contact ratings Maximum resistive-load ratings: 60 VDC / 0.3 A, 30 VDC / 1 A, or 30 VAC / 0.5 A.
Front indication / adjustment DC OK LED and +V ADJ output adjustment are shown on the mechanical drawing.

Protection thresholds describe fault response; they do not extend the permitted three-second peak duration. The DC OK relay is a monitoring contact, not an auxiliary power output.

Environment and Reliability

Working temperature / humidity −25 to +70°C subject to the stated derating; 20–95% RH, non-condensing.
Storage temperature / humidity −40 to +85°C; 10–95% RH.
Temperature coefficient ±0.03%/°C over 0–50°C.
Vibration Component: 10–500 Hz, 2G, 10 min/cycle, 60 min along each X, Y and Z axis. Mounting: compliance with IEC60068-2-6.
MTBF reference 1160.3 K hours minimum, Telcordia SR-332 (Bellcore); 169.3 K hours minimum, MIL-HDBK-217F at 25°C. These are reliability calculations, not a guaranteed service life.

For this fanless model, apply an additional ambient-temperature derating of 3.5°C per 1000 m above 2000 m. This footnote does not specify a maximum approved installation altitude.

Safety, Isolation and EMC

Catalogue approval listing UL508, TUV BS EN/EN62368-1, AS/NZS62368.1, BSMI CNS15598-1 and EAC TP TC004. The catalogue also states that the unit meets BS EN/EN60204-1.
Withstand voltage Input–output: 3 kVAC; input–FG: 2 kVAC; output–FG: 0.5 kVAC; output–DC OK: 0.5 kVAC.
Isolation resistance Greater than 100 MΩ for input–output, input–FG and output–FG, at 500 VDC, 25°C and 70% RH.
EMC emission BS EN/EN55032 (CISPR32), BS EN/EN61204-3 Class B, BS EN/EN61000-3-2 and -3, EAC TP TC020 and CNS15936.
EMC immunity BS EN/EN61000-4-2, -3, -4, -5, -6, -8 and -11; BS EN/EN55035; BS EN/EN61000-6-2 (EN50082-2); BS EN/EN61204-3, heavy-industry level; EAC TP TC020.
Voltage-sag immunity SEMI F47 approved, as listed in the catalogue.

This power supply is a component for installation in final equipment. The completed equipment must be checked again for applicable EMC compliance.

Dimensions, Terminals and Installation

Body dimensions 63 × 125.2 × 113.5 mm (W × H × D); case 979A; drawing tolerance ±1 mm.
DIN rail Compatible with TS-35/7.5 or TS-35/15; the rail drawing marks a 35 mm width.
TB1 input terminals Pin 1: FG (protective earth); pin 2: AC/N; pin 3: AC/L.
TB2 output / signal terminals Pins 1 and 2: DC OK relay contact; pins 3 and 4: +V; pins 5 and 6: −V.
Recommended full-load clearances 40 mm above, 20 mm below and 5 mm at each side. Where the adjacent device is a heat source, 15 mm clearance is recommended.
Wiring and fastening Follow the actual terminal markings and connect FG to protective earth. Use the unit’s installation instructions for conductor size and tightening torque; these catalogue pages do not give numerical limits.

Refer to PDF page 8 for the terminal layout, DIN-rail latch and body drawing. A compatible DIN rail is an installation item; its compatibility does not mean a rail is included. No separately orderable MEAN WELL bracket, cover, connector or cable accessory code is specified in these SDR-240 pages.

This model has no P suffix. Do not apply the SDR-480P parallel current-sharing specification to this model.

Weight and Manufacturer Information

Catalogue packing reference per unit 1030 g, from the PACKING entry on PDF page 7: 1.03 kg; 12 pcs / 13.4 kg / 1.22 CUFT. This is a catalogue packing reference, not a measured net or shipping weight.
Production test The manufacturer lists a 100% full-load burn-in test.
Manufacturer warranty The catalogue lists a three-year warranty, subject to the manufacturer’s applicable terms.

MEAN WELL SDR-240 series: Industrial DIN Rail Power Supply - SDR-240-48

Product form

MEAN WELL SDR-240-48 is a single-output industrial DIN rail power supply rated at 48 V DC, 5 A and 240... Read more

$202.56 Incl. VAT

    • Guaranteed secure & safe checkout.

      shop pay

    Description

    MEAN WELL SDR-240-48 is a single-output industrial DIN rail power supply rated at 48 V DC, 5 A and 240 W. It accepts 88–264 VAC or 124–370 VDC, uses free-air convection and includes active PFC, adjustable output and a DC OK relay. Peak output up to 360 W is limited to three seconds and the operating conditions below.

    Product Datasheet

    Download MEAN WELL SDR-240 Datasheet (PDF)

    The SDR-240 section is on PDF pages 7, 8, 9. Refer to the complete mechanical drawings and notes when planning installation.

    Model and Output

    Complete model SDR-240-48; SDR-240 catalogue revision 2025-02-17. The final number identifies the nominal 48 V output.
    Rated DC output 48 V / 5 A / 240 W; current range 0–5 A.
    Peak output 7.5 A / 360 W (150% of rated power), for a maximum of 3 seconds and subject to the peak-loading and derating conditions below.
    Voltage adjustment 48–55 V using +V ADJ. Observe the rated current and power limits when adjusting voltage.
    Ripple and noise 50 mVp-p maximum, measured at 20 MHz bandwidth with a 12-inch twisted pair terminated by parallel 0.1 µF and 47 µF capacitors.
    Voltage tolerance ±1%, including setup tolerance, line regulation and load regulation.
    Line / load regulation ±0.5% / ±1.0%, respectively.
    Typical efficiency 94% typical at 230 VAC, rated load and 25°C ambient; measured after 30 minutes of burn-in.

    Input and Timing

    AC / DC input 88–264 VAC or 124–370 VDC; AC frequency 47–63 Hz.
    Active PFC / typical power factor Built-in active power-factor correction; typical PF 0.94 at 230 VAC and 0.99 at 115 VAC, at full load.
    Typical AC input current 2.6 A at 115 VAC; 1.3 A at 230 VAC.
    Typical inrush current 33 A at 115 VAC; 55 A at 230 VAC.
    Leakage current Less than 1 mA at 240 VAC.
    Setup / rise time 650 / 60 ms at 230 VAC; 1300 / 60 ms at 115 VAC, at full load.
    Typical hold-up time 20 ms at both 230 VAC and 115 VAC, at full load.

    Unless otherwise stated, specifications are measured at 230 VAC input, rated load and 25°C ambient.

    Peak Loading and Derating

    Peak-duration limit Up to 360 W for no more than 3 seconds, within the permitted input and temperature conditions. Peak capability is not a continuous power rating.
    Temperature curves For vertical mounting, continuous load is 100% from −25 to +60°C, decreasing to 75% at +70°C. The three-second peak curve is 150% through +60°C, decreasing to 112.5% at +70°C.
    Input-voltage curve At 60 Hz AC, the graph shows 90% load at 88 VAC, increasing to 100% at 100 VAC and remaining at 100% through 264 VAC.
    Cooling / orientation Free-air convection; use vertical mounting for the published temperature-derating curves. Keep the ventilation path unobstructed.

    The page 9 peak-loading diagrams show two examples: 240 W for 100 seconds followed by 360 W for 3 seconds, or 120 W for 10 seconds followed by 360 W for 3 seconds. The marked 100-second and 10-second durations are the lower-load intervals, not the complete cycle periods. These examples do not establish an unrestricted duty cycle for other load patterns.

    Apply the input and temperature restrictions together; use the more restrictive allowable load. See PDF page 9 for the full curves.

    Protection and DC OK Monitoring

    Short circuit / overload The catalogue lists short-circuit protection. At 110–150% of rated output power, overload operation lasting more than 3 seconds is followed by output shutdown with automatic recovery.
    Above 150% rated power Constant-current limiting with automatic recovery within 2 seconds; operation beyond 2 seconds may cause output shutdown.
    Overvoltage 56–65 V; output shutdown, with automatic recovery.
    Overtemperature 95±5°C at TSW on the heatsink of the power switch; output shuts down and recovers automatically after cooling. This is an internal sensing temperature, not an ambient operating limit.
    DC OK relay states Contact closed: PSU turns on / DC OK. Contact open: PSU turns off / DC Fail.
    DC OK contact ratings Maximum resistive-load ratings: 60 VDC / 0.3 A, 30 VDC / 1 A, or 30 VAC / 0.5 A.
    Front indication / adjustment DC OK LED and +V ADJ output adjustment are shown on the mechanical drawing.

    Protection thresholds describe fault response; they do not extend the permitted three-second peak duration. The DC OK relay is a monitoring contact, not an auxiliary power output.

    Environment and Reliability

    Working temperature / humidity −25 to +70°C subject to the stated derating; 20–95% RH, non-condensing.
    Storage temperature / humidity −40 to +85°C; 10–95% RH.
    Temperature coefficient ±0.03%/°C over 0–50°C.
    Vibration Component: 10–500 Hz, 2G, 10 min/cycle, 60 min along each X, Y and Z axis. Mounting: compliance with IEC60068-2-6.
    MTBF reference 1160.3 K hours minimum, Telcordia SR-332 (Bellcore); 169.3 K hours minimum, MIL-HDBK-217F at 25°C. These are reliability calculations, not a guaranteed service life.

    For this fanless model, apply an additional ambient-temperature derating of 3.5°C per 1000 m above 2000 m. This footnote does not specify a maximum approved installation altitude.

    Safety, Isolation and EMC

    Catalogue approval listing UL508, TUV BS EN/EN62368-1, AS/NZS62368.1, BSMI CNS15598-1 and EAC TP TC004. The catalogue also states that the unit meets BS EN/EN60204-1.
    Withstand voltage Input–output: 3 kVAC; input–FG: 2 kVAC; output–FG: 0.5 kVAC; output–DC OK: 0.5 kVAC.
    Isolation resistance Greater than 100 MΩ for input–output, input–FG and output–FG, at 500 VDC, 25°C and 70% RH.
    EMC emission BS EN/EN55032 (CISPR32), BS EN/EN61204-3 Class B, BS EN/EN61000-3-2 and -3, EAC TP TC020 and CNS15936.
    EMC immunity BS EN/EN61000-4-2, -3, -4, -5, -6, -8 and -11; BS EN/EN55035; BS EN/EN61000-6-2 (EN50082-2); BS EN/EN61204-3, heavy-industry level; EAC TP TC020.
    Voltage-sag immunity SEMI F47 approved, as listed in the catalogue.

    This power supply is a component for installation in final equipment. The completed equipment must be checked again for applicable EMC compliance.

    Dimensions, Terminals and Installation

    Body dimensions 63 × 125.2 × 113.5 mm (W × H × D); case 979A; drawing tolerance ±1 mm.
    DIN rail Compatible with TS-35/7.5 or TS-35/15; the rail drawing marks a 35 mm width.
    TB1 input terminals Pin 1: FG (protective earth); pin 2: AC/N; pin 3: AC/L.
    TB2 output / signal terminals Pins 1 and 2: DC OK relay contact; pins 3 and 4: +V; pins 5 and 6: −V.
    Recommended full-load clearances 40 mm above, 20 mm below and 5 mm at each side. Where the adjacent device is a heat source, 15 mm clearance is recommended.
    Wiring and fastening Follow the actual terminal markings and connect FG to protective earth. Use the unit’s installation instructions for conductor size and tightening torque; these catalogue pages do not give numerical limits.

    Refer to PDF page 8 for the terminal layout, DIN-rail latch and body drawing. A compatible DIN rail is an installation item; its compatibility does not mean a rail is included. No separately orderable MEAN WELL bracket, cover, connector or cable accessory code is specified in these SDR-240 pages.

    This model has no P suffix. Do not apply the SDR-480P parallel current-sharing specification to this model.

    Weight and Manufacturer Information

    Catalogue packing reference per unit 1030 g, from the PACKING entry on PDF page 7: 1.03 kg; 12 pcs / 13.4 kg / 1.22 CUFT. This is a catalogue packing reference, not a measured net or shipping weight.
    Production test The manufacturer lists a 100% full-load burn-in test.
    Manufacturer warranty The catalogue lists a three-year warranty, subject to the manufacturer’s applicable terms.