MEAN WELL SDR-480 series: Industrial DIN Rail Power Supply - SDR-480-24

Description

MEAN WELL SDR-480-24 is a single-output industrial DIN rail power supply rated at 24 V DC, 20 A and 480 W. It accepts 90–264 VAC or 127–370 VDC, uses free-air convection and includes active PFC, adjustable output and a DC OK relay. Peak output up to 720 W is limited to three seconds and the operating conditions below.

Product Datasheet

Download MEAN WELL SDR-480 Datasheet (PDF)

The SDR-480 section is on PDF pages 10, 11, 12. Refer to the complete mechanical drawings and notes when planning installation.

Model and Output

Complete model SDR-480-24; SDR-480 catalogue revision 2025-02-17. The final number identifies the nominal 24 V output.
Rated DC output 24 V / 20 A / 480 W; current range 0–20 A.
Peak output 30 A / 720 W (150% of rated power), for a maximum of 3 seconds and subject to the peak-loading and derating conditions below.
Voltage adjustment 24–28 V using +V ADJ. Observe the rated current and power limits when adjusting voltage.
Ripple and noise 100 mVp-p maximum, measured at 20 MHz bandwidth with a 12-inch twisted pair terminated by parallel 0.1 µF and 47 µF capacitors.
Voltage tolerance ±1.2%, including setup tolerance, line regulation and load regulation.
Line / load regulation ±0.5% / ±1.0%, respectively.
Typical efficiency 94% typical at 230 VAC, rated load and 25°C ambient.

Input and Timing

AC / DC input 90–264 VAC or 127–370 VDC; AC frequency 47–63 Hz.
Active PFC / typical power factor Built-in active power-factor correction; typical PF 0.94 at 230 VAC and 0.99 at 115 VAC, at full load.
Typical AC input current 5 A at 115 VAC; 2.5 A at 230 VAC.
Typical inrush current 40 A at 115 VAC; 80 A at 230 VAC.
Leakage current Less than 0.8 mA at 240 VAC.
Setup / rise time 1500 / 150 ms at 230 VAC; 3000 / 150 ms at 115 VAC, at full load.
Typical hold-up time 14 ms at 230 VAC, at full load.

Unless otherwise stated, specifications are measured at 230 VAC input, rated load and 25°C ambient.

Peak Loading and Derating

Peak-duration limit Up to 720 W for no more than 3 seconds, within the permitted input and temperature conditions. Peak capability is not a continuous power rating.
Temperature curves For vertical mounting, the continuous-load curve at 230 VAC allows 100% through +60°C, while at 100 VAC the full-load limit is +55°C; both decrease to 80% at +70°C. The three-second peak curve has an upper envelope of 150% through +60°C, decreasing to 120% at +70°C. Apply the input-voltage limit and average-power restriction as well.
Input-voltage curve At 60 Hz AC, the graph shows 90% load at 90 VAC, increasing to 100% at 100 VAC and remaining at 100% through 264 VAC.
Cooling / orientation Free-air convection; use vertical mounting for the published temperature-derating curves. Keep the ventilation path unobstructed.

The average output power must not exceed 480 W, and each peak must last no more than 3 seconds. The second page 12 example shows 240 W for 15 seconds followed by 720 W for 3 seconds; its calculated cycle average is 320 W before applying any additional derating. Do not use a peak diagram to bypass the average-power limit.

Apply the input and temperature restrictions together; use the more restrictive allowable load. See PDF page 12 for the full curves.

Protection and DC OK Monitoring

Short circuit / overload The catalogue lists short-circuit protection. At 110–150% of rated output power, overload operation lasting more than 3 seconds is followed by output shutdown with automatic recovery.
Above 150% rated power Constant-current limiting with automatic recovery within 2 seconds; operation beyond 2 seconds may cause output shutdown.
Overvoltage 29–33 V; output shutdown, with automatic or re-powering recovery.
Overtemperature Output shutdown, with automatic recovery after the temperature decreases. The catalogue does not specify a numerical trip temperature for this model.
DC OK relay states Contact closed: PSU turns on / DC OK. Contact open: PSU turns off / DC Fail.
DC OK contact ratings Maximum resistive-load ratings: 60 VDC / 0.3 A, 30 VDC / 1 A, or 30 VAC / 0.5 A.
Front indication / adjustment DC OK LED and +V ADJ output adjustment are shown on the mechanical drawing.

Protection thresholds describe fault response; they do not extend the permitted three-second peak duration. The DC OK relay is a monitoring contact, not an auxiliary power output.

Environment and Reliability

Working temperature / humidity −25 to +70°C subject to the stated derating; 20–95% RH, non-condensing.
Storage temperature / humidity −40 to +85°C; 10–95% RH.
Temperature coefficient ±0.03%/°C over 0–50°C.
Vibration Component: 10–500 Hz, 2G, 10 min/cycle, 60 min along each X, Y and Z axis. Mounting: compliance with IEC60068-2-6.
MTBF reference 964.2 K hours minimum, Telcordia SR-332 (Bellcore); 91.9 K hours minimum, MIL-HDBK-217F at 25°C. These are reliability calculations, not a guaranteed service life.

For this fanless model, apply an additional ambient-temperature derating of 3.5°C per 1000 m above 2000 m. This footnote does not specify a maximum approved installation altitude.

Safety, Isolation and EMC

Catalogue approval listing UL508, TUV BS EN/EN62368-1, AS/NZS62368.1, BSMI CNS15598-1 and EAC TP TC004. The catalogue also states that the unit meets BS EN/EN60204-1.
Withstand voltage Input–output: 3 kVAC; input–FG: 2 kVAC; output–FG: 0.5 kVAC; output–DC OK: 0.5 kVAC.
Isolation resistance Greater than 100 MΩ for input–output, input–FG and output–FG, at 500 VDC, 25°C and 70% RH.
EMC emission BS EN/EN55032 (CISPR32), BS EN/EN61204-3 Class B, BS EN/EN61000-3-2 and -3, EAC TP TC020 and CNS15936.
EMC immunity BS EN/EN61000-4-2, -3, -4, -5, -6, -8 and -11; BS EN/EN55035; BS EN/EN61000-6-2 (EN50082-2); BS EN/EN61204-3, heavy-industry level; EAC TP TC020.
Voltage-sag immunity SEMI F47 approved, as listed in the catalogue.

This power supply is a component for installation in final equipment. The completed equipment must be checked again for applicable EMC compliance.

Dimensions, Terminals and Installation

Body dimensions 85.5 × 125.2 × 128.5 mm (W × H × D); case 984A; drawing tolerance ±1 mm.
DIN rail Compatible with TS-35/7.5 or TS-35/15; the rail drawing marks a 35 mm width.
TB1 input terminals Pin 1: FG (protective earth); pin 2: AC/N; pin 3: AC/L.
TB2 output / signal terminals Pins 1 and 2: +V; pins 3 and 4: −V; pins 5 and 6: DC OK relay contact; pins 7 and 8: NC (no connection).
Recommended full-load clearances 40 mm above, 20 mm below and 5 mm at each side. Where the adjacent device is a heat source, 15 mm clearance is recommended.
Wiring and fastening Follow the actual terminal markings and connect FG to protective earth. Use the unit’s installation instructions for conductor size and tightening torque; these catalogue pages do not give numerical limits.

Refer to PDF page 11 for the terminal layout, DIN-rail latch and body drawing. A compatible DIN rail is an installation item; its compatibility does not mean a rail is included. No separately orderable MEAN WELL bracket, cover, connector or cable accessory code is specified in these SDR-480 pages.

This model has no P suffix. Do not apply the SDR-480P parallel current-sharing specification to this model.

Weight and Manufacturer Information

Catalogue packing reference per unit 1600 g, from the PACKING entry on PDF page 10: 1.6 kg; 8 pcs / 13.8 kg / 0.9 CUFT. This is a catalogue packing reference, not a measured net or shipping weight.
Production test The manufacturer lists a 100% full-load burn-in test.
Manufacturer warranty The catalogue lists a three-year warranty, subject to the manufacturer’s applicable terms.

MEAN WELL SDR-480 series: Industrial DIN Rail Power Supply - SDR-480-24

Product form

MEAN WELL SDR-480-24 is a single-output industrial DIN rail power supply rated at 24 V DC, 20 A and 480... Read more

$299.16 Incl. VAT

    • Guaranteed secure & safe checkout.

      shop pay

    Description

    MEAN WELL SDR-480-24 is a single-output industrial DIN rail power supply rated at 24 V DC, 20 A and 480 W. It accepts 90–264 VAC or 127–370 VDC, uses free-air convection and includes active PFC, adjustable output and a DC OK relay. Peak output up to 720 W is limited to three seconds and the operating conditions below.

    Product Datasheet

    Download MEAN WELL SDR-480 Datasheet (PDF)

    The SDR-480 section is on PDF pages 10, 11, 12. Refer to the complete mechanical drawings and notes when planning installation.

    Model and Output

    Complete model SDR-480-24; SDR-480 catalogue revision 2025-02-17. The final number identifies the nominal 24 V output.
    Rated DC output 24 V / 20 A / 480 W; current range 0–20 A.
    Peak output 30 A / 720 W (150% of rated power), for a maximum of 3 seconds and subject to the peak-loading and derating conditions below.
    Voltage adjustment 24–28 V using +V ADJ. Observe the rated current and power limits when adjusting voltage.
    Ripple and noise 100 mVp-p maximum, measured at 20 MHz bandwidth with a 12-inch twisted pair terminated by parallel 0.1 µF and 47 µF capacitors.
    Voltage tolerance ±1.2%, including setup tolerance, line regulation and load regulation.
    Line / load regulation ±0.5% / ±1.0%, respectively.
    Typical efficiency 94% typical at 230 VAC, rated load and 25°C ambient.

    Input and Timing

    AC / DC input 90–264 VAC or 127–370 VDC; AC frequency 47–63 Hz.
    Active PFC / typical power factor Built-in active power-factor correction; typical PF 0.94 at 230 VAC and 0.99 at 115 VAC, at full load.
    Typical AC input current 5 A at 115 VAC; 2.5 A at 230 VAC.
    Typical inrush current 40 A at 115 VAC; 80 A at 230 VAC.
    Leakage current Less than 0.8 mA at 240 VAC.
    Setup / rise time 1500 / 150 ms at 230 VAC; 3000 / 150 ms at 115 VAC, at full load.
    Typical hold-up time 14 ms at 230 VAC, at full load.

    Unless otherwise stated, specifications are measured at 230 VAC input, rated load and 25°C ambient.

    Peak Loading and Derating

    Peak-duration limit Up to 720 W for no more than 3 seconds, within the permitted input and temperature conditions. Peak capability is not a continuous power rating.
    Temperature curves For vertical mounting, the continuous-load curve at 230 VAC allows 100% through +60°C, while at 100 VAC the full-load limit is +55°C; both decrease to 80% at +70°C. The three-second peak curve has an upper envelope of 150% through +60°C, decreasing to 120% at +70°C. Apply the input-voltage limit and average-power restriction as well.
    Input-voltage curve At 60 Hz AC, the graph shows 90% load at 90 VAC, increasing to 100% at 100 VAC and remaining at 100% through 264 VAC.
    Cooling / orientation Free-air convection; use vertical mounting for the published temperature-derating curves. Keep the ventilation path unobstructed.

    The average output power must not exceed 480 W, and each peak must last no more than 3 seconds. The second page 12 example shows 240 W for 15 seconds followed by 720 W for 3 seconds; its calculated cycle average is 320 W before applying any additional derating. Do not use a peak diagram to bypass the average-power limit.

    Apply the input and temperature restrictions together; use the more restrictive allowable load. See PDF page 12 for the full curves.

    Protection and DC OK Monitoring

    Short circuit / overload The catalogue lists short-circuit protection. At 110–150% of rated output power, overload operation lasting more than 3 seconds is followed by output shutdown with automatic recovery.
    Above 150% rated power Constant-current limiting with automatic recovery within 2 seconds; operation beyond 2 seconds may cause output shutdown.
    Overvoltage 29–33 V; output shutdown, with automatic or re-powering recovery.
    Overtemperature Output shutdown, with automatic recovery after the temperature decreases. The catalogue does not specify a numerical trip temperature for this model.
    DC OK relay states Contact closed: PSU turns on / DC OK. Contact open: PSU turns off / DC Fail.
    DC OK contact ratings Maximum resistive-load ratings: 60 VDC / 0.3 A, 30 VDC / 1 A, or 30 VAC / 0.5 A.
    Front indication / adjustment DC OK LED and +V ADJ output adjustment are shown on the mechanical drawing.

    Protection thresholds describe fault response; they do not extend the permitted three-second peak duration. The DC OK relay is a monitoring contact, not an auxiliary power output.

    Environment and Reliability

    Working temperature / humidity −25 to +70°C subject to the stated derating; 20–95% RH, non-condensing.
    Storage temperature / humidity −40 to +85°C; 10–95% RH.
    Temperature coefficient ±0.03%/°C over 0–50°C.
    Vibration Component: 10–500 Hz, 2G, 10 min/cycle, 60 min along each X, Y and Z axis. Mounting: compliance with IEC60068-2-6.
    MTBF reference 964.2 K hours minimum, Telcordia SR-332 (Bellcore); 91.9 K hours minimum, MIL-HDBK-217F at 25°C. These are reliability calculations, not a guaranteed service life.

    For this fanless model, apply an additional ambient-temperature derating of 3.5°C per 1000 m above 2000 m. This footnote does not specify a maximum approved installation altitude.

    Safety, Isolation and EMC

    Catalogue approval listing UL508, TUV BS EN/EN62368-1, AS/NZS62368.1, BSMI CNS15598-1 and EAC TP TC004. The catalogue also states that the unit meets BS EN/EN60204-1.
    Withstand voltage Input–output: 3 kVAC; input–FG: 2 kVAC; output–FG: 0.5 kVAC; output–DC OK: 0.5 kVAC.
    Isolation resistance Greater than 100 MΩ for input–output, input–FG and output–FG, at 500 VDC, 25°C and 70% RH.
    EMC emission BS EN/EN55032 (CISPR32), BS EN/EN61204-3 Class B, BS EN/EN61000-3-2 and -3, EAC TP TC020 and CNS15936.
    EMC immunity BS EN/EN61000-4-2, -3, -4, -5, -6, -8 and -11; BS EN/EN55035; BS EN/EN61000-6-2 (EN50082-2); BS EN/EN61204-3, heavy-industry level; EAC TP TC020.
    Voltage-sag immunity SEMI F47 approved, as listed in the catalogue.

    This power supply is a component for installation in final equipment. The completed equipment must be checked again for applicable EMC compliance.

    Dimensions, Terminals and Installation

    Body dimensions 85.5 × 125.2 × 128.5 mm (W × H × D); case 984A; drawing tolerance ±1 mm.
    DIN rail Compatible with TS-35/7.5 or TS-35/15; the rail drawing marks a 35 mm width.
    TB1 input terminals Pin 1: FG (protective earth); pin 2: AC/N; pin 3: AC/L.
    TB2 output / signal terminals Pins 1 and 2: +V; pins 3 and 4: −V; pins 5 and 6: DC OK relay contact; pins 7 and 8: NC (no connection).
    Recommended full-load clearances 40 mm above, 20 mm below and 5 mm at each side. Where the adjacent device is a heat source, 15 mm clearance is recommended.
    Wiring and fastening Follow the actual terminal markings and connect FG to protective earth. Use the unit’s installation instructions for conductor size and tightening torque; these catalogue pages do not give numerical limits.

    Refer to PDF page 11 for the terminal layout, DIN-rail latch and body drawing. A compatible DIN rail is an installation item; its compatibility does not mean a rail is included. No separately orderable MEAN WELL bracket, cover, connector or cable accessory code is specified in these SDR-480 pages.

    This model has no P suffix. Do not apply the SDR-480P parallel current-sharing specification to this model.

    Weight and Manufacturer Information

    Catalogue packing reference per unit 1600 g, from the PACKING entry on PDF page 10: 1.6 kg; 8 pcs / 13.8 kg / 0.9 CUFT. This is a catalogue packing reference, not a measured net or shipping weight.
    Production test The manufacturer lists a 100% full-load burn-in test.
    Manufacturer warranty The catalogue lists a three-year warranty, subject to the manufacturer’s applicable terms.