MEAN WELL HEP-2300-55HPM is a fanless industrial AC/DC power supply with a factory 55 V output and 41.8 A factory current and a 2304 W maximum-power limit. This waterproof-connector version uses PMBus and supports a configurable charging profile.
Product Datasheet
Download MEAN WELL HEP-2300 Datasheet (PDF)
The HEP-2300 section is on PDF pages 39, 40, 41, 42, 43, 44, 45, 46, 47, 48, 49, 50, 51, 52, 53, 54. Refer to the complete mechanical drawings and notes when planning installation.
Model and Configuration
Complete order code
HEP-2300-55HPM
Series
HEP-2300
Connection construction
waterproof-connector
Operating configuration
Power-supply mode by default; charging can be configured
Communication interface
PMBus
Catalogue configuration availability
By request
Ingress-protection construction
IP66
The full suffix selects the interface and construction. Catalogue availability identifies the configuration, not current distributor stock.
Terminal blank selects CANBus, and PM selects PMBus. W is the wired PV/PC version; WPM/WCAN select wired protocols. H/HPM/HMOD use waterproof connectors with CANBus, PMBus or Modbus RTU respectively.
Output Ratings and Adjustment
Factory default output voltage
55 V
Factory default output current
41.8 A
Factory default output power
2300 W
Maximum output current
48 A
Maximum rated output power
2304 W
Voltage range at maximum rated power
48–57.6 V
Ripple and noise maximum
480 mVp-p
Voltage tolerance
±1%
Line regulation
±0.5%
Load regulation
±0.5%
Output adjustment range
39–57.6 V
Voltage tolerance includes initial setting, line and load regulation. Ripple/noise is measured with 20 MHz bandwidth, a 12-inch twisted-pair lead, and 0.1 µF plus 47 µF capacitors in parallel at the output.
Observe voltage, current, rated-power and derating limits together. Maximum voltage and maximum current are not unrestricted simultaneous operating points. Use only the local or external adjustment available on this construction.
Factory voltage, current and printed power are separate catalogue entries; their rounded product does not replace the maximum-power limit.
Battery-Charging Configuration
Default boost charge voltage
57.6 V
Default float charge voltage
55.2 V
Rated charging current
40 A
Battery-capacity reference
120–400 Ah
Factory charging profile
Three stages
Three-stage charging uses constant current, constant boost voltage and then float. The two-stage curve omits float. The illustrated completion/float transition is at 10% of charging current.
The charging table lists open and sealed lead-acid batteries. The programmable description also covers lithium-ion types, including lithium iron phosphate and lithium manganese. Confirm all voltage, current, stage and timeout settings with the battery manufacturer; the suggested Ah range is not permission to exceed its charging-current limit.
Use the separately selected MEAN WELL SBP-001 smart battery-charging programmer with a PC, or the actual fitted communication protocol, to configure curves and timeout parameters.
Power-supply and charging currents are different mode ratings. Do not substitute one for the other or replace the printed power limit by multiplying rounded charging-table values.
Input Supply and Timing
AC input voltage range
90–305 VAC
DC input voltage range
250–431 VDC
AC frequency
47–63 Hz
Typical power factor
>0.99 at 115 VAC; >0.95 at 230 VAC; >0.93 at 277 VAC, full load
Typical input current
13.3 A at 115 VAC; 11 A at 230 VAC; 9.3 A at 277 VAC
Typical efficiency
95.5%
Typical cold-start inrush current
60 A at 230 VAC
Leakage current
<1.8 mA peak at 240 VAC; <2 mA peak at 277 VAC
Set-up / rise time
1800 / 100 ms at 230 VAC, full load
Typical hold-up time
12 ms at 230 VAC, full load
Unless otherwise stated, specifications are measured at 230 VAC, rated load and 25°C ambient. Active PFC is built in. Apply the input-voltage derating curve; the input range does not guarantee full output at every voltage.
Set-up and rise times refer to the first cold start. Rapid repeated switching can increase rise time.
Protection and Recovery
Overload threshold
105–115% of rated output power
Overload recovery
Constant-current limiting, then output shutdown after 5 seconds; reapply AC power
Short-circuit protection
Constant-current limiting, then output shutdown after 5 seconds; reapply AC power
Over-voltage protection
59–69.1 V; shutdown, reapply AC power
Over-temperature protection
Shutdown; automatic recovery after cooling
Auxiliary Output, Control and Status
Auxiliary output
12 V, 0.5 A, ±10%; maximum ripple 150 mVp-p
Auxiliary behaviour
Available independently of remote main-output ON/OFF
Remote ON/OFF
Short Remote ON/OFF to +12 V AUX for ON; open for OFF
DC OK relay
Closed when normal; open during alarm
AC Fail relay
Closed when AC input is normal; open during alarm
Temperature Alarm relay
Open when normal; closed during alarm
Relay contact rating
30 V maximum, 1 A maximum resistive load
AUX is a separate control supply. Do not add its current to the main output rating. Its GND-AUX return is isolated from the main DC output.
This order code supports PMBus. Use its manufacturer protocol manual for addresses, commands and bus parameters; PMBus, CANBus and RS-485 are not interchangeable interfaces.
In power-supply mode green indicates normal output and red indicates protection. During charging, orange indicates stages 1/2, green indicates float/stage 3, and red indicates protection or charging timeout. Flashing red is the approximately 95°C internal-temperature warning while output remains operating; it is not an ambient-temperature rating.
Connections, Pin Assignments and Mating Parts
AC input connector / AC input mating connector
ALTW CC-03PMMS-QC800P; ALTW CC-03BFFA-QL8APP
AC contacts and current limit / DC output 1 and 2 connectors
1 = AC/L; 2 = FG; 3 = AC/N; 20 A maximum; ALTW CC-03PMFS-QC800P
DC output 1 and 2 mating connectors / DC output 1 and 2 contacts and limits
ALTW CC-03BFMA-QL8APP; 1, 3 = +V; 2 = −V; 20 A maximum per connector
DC output 3 and battery connectors / DC output 3 and battery mating connectors
ALTW PWM-02RMFS-TS7001; ALTW PWM-02BFMB-TL7001
DC output 3 / battery contacts and rating / Alarm/control connector
1 = +V; 2 = −V; 50 A maximum connector rating; ALTW CD-12PMMS-QC8001
Alarm/control mating connector / Control pins 1 and 3
ALTW CD-12BFFA-QL8AP0; DC OK relay reference and signal
Control pin 2 / Control pin 4
Remote ON/OFF; +12 V AUX
Control pins 5 and 7 / Control pins 6 and 8
GND-AUX; AC Fail relay reference and signal
Control pins 9 and 11 / Control pin 10
Temperature Alarm relay reference and signal; SDA
Control pin 12
SCL
Connector ampere limits do not add power capacity. Keep combined outputs within 2304 W and the selected voltage/current limits. Charging is limited to 40 A; a 50 A connector does not increase charging current.
For remote ON/OFF, short pin 2 to AUX pin 4 for ON and leave it open for OFF. Relay references are separate from the AUX return. Use the listed ALTW assemblies or suitable equivalents, maintain polarity, and seal unused ports with the appropriate optional caps.
Environment and Derating
Working ambient temperature
−40 to +70°C, subject to load and orientation
Working humidity
20–95% RH, non-condensing
Storage temperature
−40 to +85°C
Storage humidity
10–95% RH, non-condensing
Temperature coefficient
±0.03%/°C from 0 to 50°C
Vibration
20–500 Hz, 10G; 12 minutes/cycle, 72 minutes each along X, Y and Z
Cooling and case
Fanless conduction cooling; aluminium case filled with heat-conducting glue
Catalogue warranty
6 years
For operation above 2000 m, reduce the permitted ambient temperature by 3.5°C for each additional 1000 m for this fanless supply. Follow the stated orientation and mounting clearances.
Horizontal mounting permits full load through +40°C and reduces to 60% at +60°C. Vertical mounting permits full load through +50°C and reduces to 60% at +70°C. Do not extend the horizontal curve beyond its plotted +60°C endpoint.
The 60 Hz input curve shows 50% load at 90 VAC, 60% at 115 VAC and full load from 220 through 305 VAC. Apply input and temperature derating together.
The catalogue life reference is at least 55,000 hours when the marked case temperature Tc is approximately 80°C or less. The temperature-dependent life plot is a design reference, not a warranty extension.
The charging specification lists storage at −40 to +80°C; the power-supply specification lists −40 to +85°C. Use the applicable mode specification.
Dimensions, Mounting and Weight
Catalogue body dimensions
375 × 280 × 88 mm
Catalogue packing reference per unit
12500 g
Standard mounting-plate envelope references
447 mm length; 91 mm height
Bottom mounting
Four M6, L = 25 mm screws
Side mounting
Two M6, L = 15 mm screws
This is the catalogue packing reference per unit, not a measured net or parcel mass. The table lists 12.5 kg per unit and one unit per 13.5 kg carton.
Allow connection and cable clearance separately from body dimensions.
Use the mounting drawing’s edge-reference coordinates for hole positions and apply the corresponding horizontal or vertical thermal curve.
Rear pole mounting uses PGG2BKT-003 with PGG2BKT-004. Side pole mounting uses PGG2BKT-001, PGG2BKT-002 and PGG2BKT-004. The illustrated pole installation has the AC-input side downward.
Compatible Optional Equipment
Optional housing-side bracket
PGG2BKT-001
Optional pole-side bracket
PGG2BKT-002
Optional rear plate
PGG2BKT-003
Optional pole-attachment kit
PGG2BKT-004
Charging-curve programming option
SBP-001 for the fitted supported protocol
Cap for output 3 and battery-charger ports
PFF1ZAHB-A0025(A)
Cap for AC input, output 1/2 and alarm/control ports
PFF1CAP-WACMQMA1(B)
Select only the items listed here for the stated construction and purpose. Optional items are selected separately according to the actual order; an installation illustration does not establish package contents.
Safety, EMC and Reliability
Safety approvals
UL62368-1; TUV BS EN/EN62368-1; EAC TP TC 004
Input-to-output withstand
6 kVDC
Input-to-FG withstand
4 kVDC
Output-to-FG withstand
4 kVDC
Insulation resistance
100 MΩ at 500 VDC, 25°C, 70% RH
Minimum MTBF, Telcordia SR-332
478 k hours
Minimum MTBF, MIL-HDBK-217F at 25°C
44.8 k hours
Over-voltage category
OVC III
BS EN/EN61558-1 and BS EN/EN60335-1 are design references available by request; this does not constitute approval of the complete installation.
Conducted emissions follow BS EN/EN55032 (CISPR32) Class B. Radiated emissions are Class A. Harmonic current follows BS EN/EN61000-3-2 Class A; flicker follows BS EN/EN61000-3-3.
Immunity references are BS EN/EN55024 and BS EN/EN61000-6-2: ESD 8 kV air / 4 kV contact; radiated immunity and EFT level 3; surge 2 kV line-to-line / 4 kV line-to-earth; conducted immunity level 3; magnetic-field level 4. Dips include >95% for 0.5 period and 30% for 25 periods, with >95% interruption for 250 periods.
This is a component for installation in finished equipment. Confirm EMC in the final system. The test setup uses a 1100 × 650 × 1 mm metal plate. For the specified isolation test, temporarily remove the identified Screw A and reinstall it afterward.